30
C048-741-30 R01, Rev. B (01/2020)
6.8
6.8 Realtime Status
Realtime Status
By clicking on the
Realtime Status tab located at the top of
the home page, BDFB bus and panel detail will be shown (see
Figure 70 & 71).
For bus detail, a table will display:
y
Bus number
y
Load
y
Feeder fuse size
y
Voltage
For panel detail, a table will display:
y
Panel communication status
y
Channel number
y
Load per channel
y
Ampacity per channel
y
Inventory per channel (yes/no)
y
Breaker status per channel (on/off)
Alarms: If communication with a panel is lost, Comms Lost will
appear with a red background at the top of the Panel Detail
table. If communication is not lost, Comms OK will appear with
a green background. See Table 21 below for inventory and
breaker status alarms.
Table 21. Inventory and Breaker Status Alarms
ALARM
COLOR
CAUSE
Minor
Orange
Breaker not inventoried;
Breaker ON
Major
Red
Breaker inventoried;
Breaker OFF
6.9
6.9 Administration Home
Administration Home
To access the configuration settings of your embedded
ethernet module, select the Administration tab located at the
top of the home page.
6.9.1
6.9.1
Notification Settings
Notification Settings
This page allows the user to specify the SNMP and email
notification settings (See Figure 72).
Figure 70. Bus Detail
Figure 71. Panel Detail
Figure 72.
Notification Settings