WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage
or blindness. Never operate the HEPS System out of the ductwork. Avoid touching the glass portion of the lamp with your hands.
The Hi-Velocity Air Purification System installs in the
air-inlet side of the Hi-Velocity unit up to five tons in size.
Before installing the Hi-Velocity Air Purification System,
inspect for any signs of damage.
Warning -
Always
unplug the power cord from the
HEPS System when changing the filter or ultraviolet lamps.
Never
look into a burning ultravioletlamp without proper
eye protection as sever damage to the eyes can result.
This product is rated for standard ambient air temperatures
during heating and air-conditioning functions and not
rated for elevated air temperatures in excess of 125
degrees fahrenheit.
Do not
attempt to clean the catalytic aluminum substrate
with cleaning solutions. The catalyst is radiated with short
wave ultraviolet light during period of non-air fl ow and
is self-cleaning. If there is build up blocking the catalytic
cells, sit the unit on end, on a fl at surface, with electrical
enclosure facing up. Use low-pressure, compressed air to
blow the surface of the catalytic cells free of blockage.
Do not
install insulation within 76MM or 3 inches of
Luminaries.
Access for service is required when mounting above
ceilings or behind walls.
Do not
install in a position where the
interior module
can gravity fall from an elevated position and cause injury
to people or equipment below.
Installation
Make sure to install the Hi-Velocity Air Purification System
so that the inlet or return air enters the side containing the
MERV particle filter first
(Fig. 1)
.
Fig. 1 HEPS Air Flow
Typical Horizontal and Vertical Installation
(Fig. 2, Fig. 3)
1.
Unscrew the two locking knobs and remove the
inside components from the outer case.
2.
Take care not to bend or distort the outer metal
enclosure.
3.
Mount the outer case to the support plenum Note:
Do not use a screw length that will extend into or penetrate
the inside module containing the catalyst or filter.
HEPS
RPM-E
Air Handler
Air Flow
Fig. 2 Horizontal Installation
IMPORTANT SAFETY INSTRUCTIONS
FILTER SIDE
CATALYST SIDE
AIR FLOW
Fig. 3 Vertical Installation
4.
When installing the HEPS to a Hi-Velocity 50 or 70 fan
coil, a transition should be made (
Fig. 4)
or simply block
air flow with a piece of sheet metal
(Fig. 5)
.
RBM Cooling
Coil
Air Flow
Air Handler
HEPS