Rev 03/12/14 ENERGY KING
®
385EK Wood/Coal Furnace Owner’s Manual
U. S. 15
Installation
c.
Set Pointers.
Hold dial securely with one
hand and move the pointers with the other
hand. Do not force the pointers past any
stops on the dial even though the dial may
be graduated beyond the stops.
i.
Limit.
Verify that the right hand pointer
is set at 200-degrees F. This is the
temperature at which contacts should
open to prevent your Furnace from
overheating. Never set the Limit pointer
higher than 200-degrees F, as
recommended by the Fan/Limit Control
manufacturer.
ii.
Fan
. Move the “Fan On” pointer so that
its straight edge indicates the
temperature at which the fan contacts
should close to start the blower. Move
the “Fan Off” pointer so that its straight
edge indicates the temperature at which
the fan contacts should open to stop the
blower. Recommended “Fan On” setting
is 145-
degrees F. Recommended “Fan
Off” setting is 90-degrees F.
8.
Circulation Blower
.
a. Mount circulation blower on rear of furnace
using the four bolts supplied.
b. If you selected the optional Filter Box kit,
proceed to step 9. Otherwise, attach the
conduit to Control Box and connect wire
ends as detailed in
Appendix A: Wiring
Diagrams
.
Do not connect power to your
ENERGY KING Wood/Coal Furnace until
the installation is complete.
9.
Cold Air Return & Optional Filter Box.
a. Determine whether your cold air return will
enter on the left or right side of the furnace.
b. Assemble the optional filter box per
Appendix B: Filter Box Assembly
Schematic
.
c. Feed the conduit from your circulation
blower through the hole located on the top
of the filter box. Attach the conduit to
Control box and connect wire ends as
detailed in
Appendix A: Wiring Diagrams
.
Do not connect power to your
ENERGY KING Wood/Coal Furnace until
the installation is complete.
10.
Wiring.
Do not connect power to your
ENERGY KING Wood/Coal Furnace until
the installation is complete.
Once you’ve completed the installation of
your ENERGY KING Wood/Coal Furnace,
you may connect your 110V power supply to
the left side of the control box. Wiring is
based on draft choice. Please see
Appendix
A: Wiring Diagrams
.
Risk of electric shock.
Disconnect power at the
service panel or breaker box
before servicing ENERGY KING
Wood/Coal Furnace.
Figure 8: Fan/limit Control Settings
Recommended “Fan Off” setting is 90 º F.
Recommended “Fan On” setting is 145º F.
Содержание 385EK
Страница 2: ......
Страница 4: ......
Страница 8: ...Rev 03 12 14 ENERGY KING 385EK Wood Coal Furnace Owner s Manual U S 2 ...
Страница 46: ...Rev 03 12 14 ENERGY KING 385EK Wood Coal Furnace Owner s Manual U S 40 This page is intentionally left blank ...
Страница 47: ...Rev 03 12 14 ENERGY KING 385EK Wood Coal Furnace Owner s Manual U S 41 Appendix C Firebrick Layout ...
Страница 48: ...Rev 03 12 14 ENERGY KING 385EK Wood Coal Furnace Owner s Manual U S 42 This page is intentionally left blank ...
Страница 52: ...Rev 03 12 14 ENERGY KING 385EK Wood Coal Furnace Owner s Manual U S 46 This page is intentionally left blank ...
Страница 56: ...Rev 03 12 14 ENERGY KING 385EK Wood Coal Furnace Owner s Manual U S 50 This page is intentionally left blank ...
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......