Operating Manual
Arc fa
ult protection ZŁ-4A; (07.2019)
93
MxA, MxB
Cx optical sensor working mode
0 0
Inactivated
0 1
Optical sensor Cx tripping in zone Z1
1 0
Optical sensor Cx tripping in zone Z2
1 1
Optical sensor Cx tripping in zone Z3
Register: UnitsConfig.FlashTestStatus
MxA, MxB
Optical sensors test status
0 0
test has not been performed
0 1
test performed but the sensor not checked (off in the bay unit)
1 0
test performed but the sensor damaged
1 1
test performed and the sensor operational
bit
7
6
5
4
3
2
1
0
C4A
C4B
C3A
C3B
C2A
C2B
C1A
C1B