Light commercial(High ESP Duct 196Pa) Service Manual
51
◇
Intelligent defrosting function(only in the case of outdoor coil is damaged this function is
carried out)
Entering conditions
On the condition of running intelligent defrosting operation, one of following 7 conditions is satisfied
(As for secondary condition in upper condition, it is only valid that all secondary condition be
satisfied at the same time)
a) Condition No.1
①
The outdoor fan enters into over-load protection and stops running.
②
Outdoor fan stops running then restarts and keeps running over 10 min
③
The compressor accumulating running time ≥45min
④
The compressor continuous running time ≥20min
⑤
TE ≤ 48
℃。
b) Condition No.2
①
Enter into heating mode 5 min later or finish defrosting 5 min later, catch the max
difference
value between TE and TA
If TE≥38
℃,
when the difference between TE and TA decrease by 5
℃
or more and lasting
time ≥3min
If the difference between TE and TA decrease by 3
℃
or more and lasting time ≥3min
②
The compressor continuous running time ≥5min
③
Th
e compressor accumulating running time ≥45min
④
TE ≤ 48
℃;
Note: If there is wind modification, and when indoor fan wind speed descends 1 grade, temperature
modification -1
℃
.when indoor fan wind speed climbs 1 grade, temperature modifi1
℃
c) Condition No.3
①
The compressor accumulating running time ≥3h
②
The continuous compressor running time ≥5min
③
The min. difference between TE and TA
<
16
℃
d) Condition No.4
①
The min. difference between TE and TA
<
16
℃
continuously last for 5 min
②
The comp
ressor accumulating running time ≥45 min
③
The compressor continuous running time ≥20min
If the condition is satisfied unit will enter into defrosting, current TE will be recorded before
defrosting. When the defrosting is over, and the compressor continuously runs for 10 min,
then compare current TE with TE before defrosting, if the latter doesn’t high than former by
3
℃
or more, next time unit will not enter into defrosting at this condition, until mode switch,
turn off then restart to heating or go through a defrosting yet.
e) Condition No.5
Begin to calculate time once air conditioner enters into over-heating protection, enters into
compulsory defrosting after 2 h later.
f) Condition No.6
①
5 min later after enters into heating mode for the first time, catching max value of TE, if TE
<
38
℃
②
The compressor continuous running time ≥5min
Содержание SAD48HD1-A
Страница 18: ...Light commercial High ESP Duct 196Pa Service Manual 17 3 2 Outdoor Unit SAU48U1 A SAU60U1 A...
Страница 33: ...Light commercial High ESP Duct 196Pa Service Manual 32...
Страница 35: ...Light commercial High ESP Duct 196Pa Service Manual 34...
Страница 37: ...Light commercial High ESP Duct 196Pa Service Manual 36...
Страница 56: ...Light commercial High ESP Duct 196Pa Service Manual 55...
Страница 58: ...Light commercial High ESP Duct 196Pa Service Manual 57 Communication failure between indoor and outdoor unit...
Страница 59: ...Light commercial High ESP Duct 196Pa Service Manual 58...
Страница 60: ...Light commercial High ESP Duct 196Pa Service Manual 59 Outdoor protection phase sequence...
Страница 61: ...Light commercial High ESP Duct 196Pa Service Manual 60 Cooling high pressure protection...
Страница 62: ...Light commercial High ESP Duct 196Pa Service Manual 61 Heating high pressure protection...
Страница 63: ...Light commercial High ESP Duct 196Pa Service Manual 62...
Страница 64: ...Light commercial High ESP Duct 196Pa Service Manual 63 Cooling low pressure protection...
Страница 65: ...Light commercial High ESP Duct 196Pa Service Manual 64 Heating low pressure protection...
Страница 66: ...Light commercial High ESP Duct 196Pa Service Manual 65...
Страница 67: ...Light commercial High ESP Duct 196Pa Service Manual 66 Cooling exhaust temperature protection...
Страница 68: ...Light commercial High ESP Duct 196Pa Service Manual 67 Heating exhaust temperature protection...
Страница 70: ...Light commercial High ESP Duct 196Pa Service Manual 69 Sensor failure protection...
Страница 71: ...Light commercial High ESP Duct 196Pa Service Manual 70...
Страница 73: ...Light commercial High ESP Duct 196Pa Service Manual 72 5 2 2 Air conditioner operates but effect is terrible...
Страница 74: ...Light commercial High ESP Duct 196Pa Service Manual 73...
Страница 75: ...Light commercial High ESP Duct 196Pa Service Manual 74...
Страница 76: ...Light commercial High ESP Duct 196Pa Service Manual 75 5 2 3 Abnormal sound or viberation...
Страница 77: ...Light commercial High ESP Duct 196Pa Service Manual 76...
Страница 78: ...Light commercial High ESP Duct 196Pa Service Manual 77...
Страница 79: ...Light commercial High ESP Duct 196Pa Service Manual 78 5 2 4 Abnormal odor...
Страница 80: ...Light commercial High ESP Duct 196Pa Service Manual 79 5 2 5 Air switch action when air conditioner starting up...
Страница 81: ...Light commercial High ESP Duct 196Pa Service Manual 80 5 2 6 Air conditioner water leakage...