![Energie FF Evi 10 Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/energie/ff-evi-10/ff-evi-10_installation-and-instruction-manual_2409982040.webp)
ENERGIE
Page | 38
FAN
F03
Minimum fan speed
%
20
F04
Maximum fan speed
%
100
F05
Setpoint to increasing or keep constant the fan speed
bar
(abs)
13
F06
Setpoint to put the fan at maximum speed.
F
maxspeed
→ B04 > F05+F06
bar
(abs)
2
F07
Setpoint to turn OFF the fan.
F
OFF
→ B04 > F05-F07
bar
(abs)
6
F08
Setpoint to increasing or keep constant the fan speed
bar
(abs)
5,5
F09
Setpoint to put the fan at maximum speed.
F
maxspeed
→ B04 < F08 – F09
bar
(abs)
1,5
F10
Setpoint to turn OFF the fan.
F
OFF
→ B04 > F08 + F10
bar
(abs)
2
F13
Fan OFF during the defrost cycle
int
2
CONTROL
R01
Heating setpoint
°C
12
R02
Differential of R01
°C
3
R03
Cooling setpoint
°C
50
R04
Differential off R03
°C
5
R22
Second setpoint
°C
53
1
1
8
8
.
.
C
C
o
o
n
n
t
t
r
r
o
o
l
l
l
l
e
e
r
r
S
S
Y
Y
S
S
B
B
18.1
Protection module