ENERGIE
Page | 23
“Direct”:
accessible by pressing “
” for 5 s, it allows to read the probes
and any data, which can be interrogated by anyone without compromising
unit operation.
16.7
Parameters modification procedure
a. Press “
“ and “
” for 5 s;
b. The
and symbols appear along with “00”;
c. Set the password via “
” or “ ” and confirm with “
“;
d. Select the parameters menu (S-P) via “
” or “ “. Confirm with “
”;
e. Select the parameters category (A,b,c,d..) via “
” or “ “. Confirm
with “
”;
f. Select the parameter via “
” or “ “. Confirm with “
”;
g. Modify the parameter value with “
” or “ ;
h. After modification, press “
” to confirm or “
” to annul the
modification;
i. Press “
” to return to the previous menu;
j. To save the modifications, press “
” several time until going back
to the main menu;
ATTENTION
The parameters modified without confirmation via the “
” key go
back to the previous value;
If no operations are performed on the keyboard for 60 seconds, the
controller exits the parameter modification menu by timeout and the
changes are cancelled.
16.8
Configure/ change cooling and heating set points
Parameter
Description
r01
Setpoint cooling mode
r02
Differential of r01.
r03
Setpoint heating mode
r04
Differential of r03.
To configure the cooling and heating set points in the Heat Pump must
perform the following procedures:
a. Go to the controller “µC²SE”,
b. Press simultaneously the "
" keys during 5 s;