14.8.
Room thermostat installation
The thermostat must be installed:
•
an interior wall about 1.5m from floor level
•
a place where the temperature is uniform.
•
a place where have a good circulation of air around the thermostat.
The thermostat cannot be installed:
•
in exterior walls.
•
near the radiators, convectors, etc.
•
behind or near the doors.
•
near to the windows.
14.9.
Electrical wiring
Model
Power source
Max. current
* Power source
cable section
AP X30
400V~ /3F+N/ 50Hz
36 A
6 mm²
*
The above wire sizes are
selected at the maximum current of the unit
according to the European Standard EN60335-1 and
considering a cable
length of 10 meters.
Select the main switches according to the next table:
Model
Power source
Max.
current
CB
ELB
(no.
poles/A/mA)
AP X30
400V~/3F+N/50Hz
36A
40 A
4/40/30
CB – Circuit breaker; ELB – Earth leakage breaker