ENERGIE
Page | 38
36
CN4
No use
37
CN5
Color screen, DC fan speed regulation module,
inverter board
38
CN15
DTU
39
RO15
No use
40
RO14
No use
41
RO13
No use
42
RO12
Alarm output
43
RO11
Chassis heating tape
44
RO10
Crankshaft heating tape
45
RO09
Hot water three-way valve
46
RO08
Electrical heating level 2
47
RO07
Electrical heating level 1
48
RO06
4-way valve
50
RO05
Domestic hot water pump
51
RO04
Main circulating water pump
52
RO03
Fan low speed
53
RO02
Fan high speed
54
RO01
Compressor 1
19.
Troubleshooting and Additional Information
Failure
Possible causes for the
failure
Solutions
BC does not work, display
without information
1) Power supply failure.
2) Circuit breaker off.
3) Power cable not
properly connected.
4) Swapped phases.
5) Blown controller fuse
1) Check the power supply.
2) Check if there is an anomaly
and turn the circuit breaker back
on.
3) Connect the power cord
correctly.
4) Change one of the phases.
5) Check the fuse
Water pump is running with high
noise or without water
1) Lack of water. in the
hydraulic circuit,
2) Air in the installation
3) Valves closed
4) Dirty or clogged
water filter
1) Check that there is no water
leak. Fill the circuit
2) Purge the hydraulic circuit.
3) Open the valves
4) Clean the filter
Содержание Aquapura 12