SAFETY TIMER – EMERGENCY STOP
•
If the battery doesn't reach the gassing voltage within 12 hours, the charge is terminated by
the Emergency timer. The display will show the error message “Time Error”:
If this error message appear, it's recommended to call the service for a complete check of the
system.
The cause if this problem may be a wrong setting of the input voltage: if the input is set to a
certain value (for example: 610 V) but the real voltage is lower (for example: 575 V), the charging
current will be significantly lower than the nominal value, therefore it will take more time to
reach the gassing voltage.
AUTOMATIC DATA SAVING
•
If, while the charge or the equalization are in progress, a black-out of the AC input occurs, the
charger saves automatically all the relevant information about the state of the charge.
While the input power is absent, the message “Black Out” is displayed:
•
When the power supply will be available again, the charger will re-start automatically from the
exact point of interruption, and the charge will be normally completed.
AUTOMATIC AND MANUAL CHARGE TERMINATION
•
AUTOMATIC CHARGE TERMINATION:
When the charge has been normally completed, the charger turns off automatically.
The display shows the flashing message “End”.
At this point, it's possible to disconnect the battery.
OWM-AR-D-[]
Page 19 of 23
WARNING !
DON'T disconnect the battery from the charger while it is being charged.
ARCING AND BURNING OF CONNECTORS OR BATTERY EXPLOSION MAY RESULT!