Battery Charger RLD
User's Manual
BATTERY CONNECTION, VOLTAGE CHECK AND AUTOSTART
•
Connect the battery to the charger, using an adequate connector.
When the battery is correctly connected, the display will show the battery voltage.
If the battery voltage is below the minimum threshold of 1,62 V/cell, the charger will not start,
and the display will show the error message “Voltage Low”:
If the battery voltage is higher than the maximum threshold of 2,60 V/cell, the charger will not
start, and the display will show the (flashing) error message “Voltage High”:
If the battery voltage is between the minimum and maximum thresholds, the charger will turn on
automatically after 5 seconds.
If, during the charge, the battery voltage exceeds the maximum threshold of 2,80 V/cell, the
charger will shut down automatically, and the errore message “Voltage High” will appear on the
display.
CHARGE PROCESS
While the charge is in progress, the following parameters are continuously displayed in
sequence:
•
Battery Voltage/cell
(Output voltage)
(U)
(Volt);
•
Charge current
(Output current)
(A)
(Ampere);
•
Effective time of charge
(h)
(Hours);
•
Capacity charged
(C)
(Ah);
The letter after the value (U-A-h-C) indicates which parameter being is displayed.
To display the time, the charger uses this format:
OWM-AR-D-[]
Page 16 of 23
CAUTION !
ENERGIC Plus RLD
chargers are programmed to do a complete cycle of charge
automatically, however it’s always recommended to survey the operations, especially
when the battery is connected to the charger for more than 12 hours.