Enerflow generation 5 Скачать руководство пользователя страница 22

22

Every household’s daily hot water consumption profile is different and therefore not 
all timer settings could be the same.  However, this section may be used as a guideline 
that can be followed to enhance energy saving.  The assumption made herein is that 
no large quantity of hot water will be consumed before 13h00-14h00 and that the 
majority of hot water is consumed between 19h00-21h30.

ON 1:

 This is used to turn the heat pump 

on, and should be set to as late as 

possible in the early afternoon i.e. 14h00. 

OFF 1:

 This is used to turn the heat pump 

off and should be set to 1 hour after the 

family has gone to bed e.g. 23h00, thus 

leaving geyser with hot water ready to be 

used for the morning showers etc. 

ON 2:

 This is used to activate the second 

timeslot at which the heat pump should 

turn on, and should be set to 1-2 hours 

before hot water is to be consumed in 

the morning. The heat pump will further 

heat the water that may not have been 

heated by ON1 and also recover the heat 

loss of the geyser during the night.

OFF 2:

 This is used to deactivate the 

second timeslot and should be set to 

heat just enough water for morning 

consumption (i.e. two showers).  It is best 

to let the heat pump deactivate before 

consumption starts.

Below are some examples of timer settings to guide the user.

NOTE:

• 

The LCD controller will turn off the internal components of the heat pump and 

enter into standby mode when the desired set water temperature is reached.  

During this time, the water temperature will be monitored and if the temperature 

falls below the set temperature (see allowed temperature deviation as set in 

Parameter 1) the heat pump will start heating the water again.  Thus, it is important 

to note that the timer settings allows the heat pump to operate during that 

specified interval only.

• 

The Enerflow heat pump may heat the geyser faster than an electrical element 

in outside air temperatures higher than 18°C, but may take longer when outside 

air temperatures are below 18°C. Therefore the timers should allow the heat 

pump to reheat the water as long as the conditions outside is favourable.

Suggested timer settings

8.3

ON 1:

08:00

OFF 1:

23:00

ON 2:

04:00

OFF 2:

05:00

ON 1:

11:00

OFF 1:

23:00

ON 2:

04:00

OFF 2:

05:00

Example 1:

 For a family with someone at 

home during the morning.

Example 2:

 For a family not home during 

the morning.

 

FOR INFORMATION ONLY 

Configuration Management 

M-Tech Industrial (Pty) Ltd 

 

Содержание generation 5

Страница 1: ...Residential Heat Pump USER GUIDE Please read this guide before operating the heat pump GENERATION 5 FOR INFORMATION ONLY Configuration Management M Tech Industrial Pty Ltd...

Страница 2: ...g Parameters 13 7 MAINTENANCE AND SERVICING 15 7 1 Self maintenance by the user 15 7 1 1 Cleaning the strainer 15 7 1 2 Other general maintenance considerations 16 7 2 Annual service performed by the...

Страница 3: ...ed in SANS 10142 WARNING Do not turn off main power supply to the heat pump during a vacation or if not in use The heat pump must have electricity in order to protect itself during cold climate condit...

Страница 4: ...board DB the intelligent controllerwill start up and displaythe initialization phase for a few seconds after which the time will be displayed as 00 00 The unit is now in standby mode and ready for op...

Страница 5: ...ion and should only be used in the exemption when reheating time needs to be reduced due to a temporary higher demand of hot water WARNING Do not turn off main power supplyto the heat pump during a va...

Страница 6: ...position will now be flashing 5 Make use of the buttons to change the Minutes Change to the current Minutes 6 Press SET to acknowledge the Minutes setting Time Setting NOTE To lock or unlock the inte...

Страница 7: ...owed to overlap The table illustrates an incorrect timer setting where time zone 1 and time zone 2 overlaps with a resulting allowed operational time in column 3 3 Press the button to acknowledge the...

Страница 8: ...ligent controller directly to the electric element Auto Heat pump operation On Backup element only Once the power is switched over to the electric element it will be controlled by the element thermost...

Страница 9: ...on Cycle the sign will flash on the LCD controller The pathogenic Gram negative bacterium that grows in central heating and air conditioning systems at a certain temperature that can cause Legionnaire...

Страница 10: ...hot water on tap solution The installer will ensure that the commissioning valve on the return line is set to an approximate 10 bypass i e closed 90 Activate the micro circu lation function by changi...

Страница 11: ...g interval 30 90 min 40 min Do not change 3 Temperature at which defrosting operation starts 30 0 C 7 C Do not change 4 Temperature at which defrosting operation stops 2 30 C 13 C Do not change 5 Dura...

Страница 12: ...surement probe offset 10 10 C 3 C Do not change 20 Automatic geyser temperature measurement probe offset 0 fixed 1 calculated 0 Do not change 21 EEV setting 0 5 0 5 See remarks at the end of the table...

Страница 13: ...as 4 for ERHP SU20E MS ERHP SU20E PL Parameter 21 should be set as 5 for ERHP SU26E MS To adjust or change the parameter settings follow the steps below If the target temperature needs to be changed p...

Страница 14: ...te If both continue to flash please ensure the heat pump is in Standby mode 3 Make use of the buttons to change the value to the desired or default value 4 PresstheSETbuttontoconfirmthesettingandretur...

Страница 15: ...he strainer by using the correct size spanner 3 Remove the strainer element or Sieve 4 Rinse and clean the strainer element under running water by slightly opening the inlet ball valve 5 Reinsert the...

Страница 16: ...ent at all times Ensure that the geyser tank probe is still correctly inserted and fastened into the geyser probe pocket or onto the geyser flange Open and service the water circulation pump Ensure th...

Страница 17: ...t running Check the air temperature Clean the finned coil as per maintenance section Remove the obstacle Contact the installer P01 Water inlet temperature sensor failure In case of any of these failur...

Страница 18: ...30 seconds and switch on again Clean inline water strainer Check municipal water supply pressure Contact the installer to open and clean water circulation pump E06 LP switch failure Contact the instal...

Страница 19: ...water to the geyser If the temperature decreases the fan will resume operation again 4 If the unit enter the defrosting mode the fan may stop working temporarily Once the evaporator coil temperature...

Страница 20: ...s and enhance heat transfer This absorbed heat energy is then further intensified i e more energy added by passing the gas through the compressor which increases the pressure and temperature of the ga...

Страница 21: ...n this picture it can be clearly seen that the heat pump will save more energy i e money at higher outside air temperatures The picture below depicts the typical average daily ambient temperature on a...

Страница 22: ...ust enough water for morning consumption i e two showers It is best to let the heat pump deactivate before consumption starts Below are some examples of timer settings to guide the user NOTE The LCD c...

Страница 23: ...ssor unit of the product 2 The warranty will only be valid provided that proof of the correct installation commissioning and operating procedures as set out during training and certification were foll...

Страница 24: ...ted as a result of acts of God including damage due to extreme cold and frost or Force Majeure 4 Notwithstanding the provisions where goods are to be manufactured to the instructions drawings or speci...

Страница 25: ...are comprehensively completed by boththe client andthe installerto ensurethewarrantyonthe heat pump is instated Heat Pump Serial Number Installation date INSTALLER DETAILS Company Name Reference Numb...

Страница 26: ...26 FOR INFORMATION ONLY Configuration Management M Tech Industrial Pty Ltd...

Страница 27: ...27 Please visit www enerflow co za for the performance specifications of your specific heat pumpmodel Performance Specifications FOR INFORMATION ONLY Configuration Management M Tech Industrial Pty Ltd...

Страница 28: ...chefstroom South Africa 27 0 18 297 0326 7 27 0 18 297 0318 rhp enerflow co za Tel Fax Email SWIMMING POOL HEAT PUMPS Harvests free thermal energy from the atmosphere and transfers it to your pool FOR...

Отзывы: