µDIGI2-E
µDIGI2-E
43
EMI max. Influence (0-1A) ............................................ ±1mA
EMI max. Influence (0-5A) ............................................ ±5mA
EMI max. Influence (Shunt 60mV) ................................ ±60
µ
V
EMI max. Influence (Shunt 100mV) ............................ ±100
µ
V
DIMENSIONS
Dimensions ................................... 96 x 48 x 60 mm (1/8 DIN).
Panel cut-out ....................................................... 92 x 45 mm.
Weight .......................................................................... 150g.
Case material ................................... UL 94 V-0 polycarbonate.
RELAY OUTPUT OPTION
Maximum switching current (resistive load)
......................... 8A
Maximum switching power .............................. 2000VA / 192W
Maximum switching voltage .......................... 400VAC / 125VDC
Contact rating ....................................... 8A @ 250VAC / 24VDC
Contact resistance ..............................
≤
100m
Ω
at 6V DC @ 1A
Contact type .................................................................. SPDT
Operate time ...............................................................
≤
10ms
NOTE:
In case that the outputs are used to drive inductive
loads, it is recommended to add an RC network between
the coil terminals (preferably) or between the relay
contacts, to limit electromagnetic effects and to extend
contacts life.
RANGE
RESOLUTION
ACCURACY (45Hz-1kHz)
0-1A
50
µ
A
±(0.1%rdg + 5mA)
0-5A
200
µ
A
±(0.1%rdg + 20mA)
Shunt 60mV
5
µ
V
±(0.1%rdg + 300
µ
V)
Shunt 100mV
10
µ
V
±(0.1%rdg + 300
µ
V)