U
SER MANUAL
–
ENERIUM
100/200/300
MS1-7352 ENERIUM100/200/300_ Ed04 User Manual
Page 69 / 86
21 C
HARACTERISTICS
The so-called instantaneous quantities are refreshed every second, except for THDs, which are
refreshed every six seconds.
The average quantities are calculated on a programmable basis from 0 to 30 minutes. These quantities
are updated every tenth of a period.
21.1 Measurements
Quantity
1S
MIN
MAX
AVG
MIN AVG
MAX AVG
V1, V2, V3, VGround
●
●
●
●
●
U12, U23, U31
●
●
●
●
●
I1, I2, I3, In
●
●
●
●
●
P1, P2, P3
●
●
(1)
●
(1)
Pt
●
●
(1)
●
(1)
●
(1)
●
(1)
Q1, Q2, Q3
●
●
(1)
●
(1)
Qt
●
●
(1)
●
(1)
●
(1)
●
(1)
S1, S2, S3
●
●
●
St
●
●
●
●
●
FP1, FP2, FP3
●
●
(1)
FPt
●
●
(1)
●
(1)
●
(1)
Cos
φ
1, Cos
φ
2, Cos
φ
3
●
●
(1)
Cos
φ
t
●
●
(1)
●
(1)
●
(1)
Tan
φ
●
●
(1)
●
(1)
●
(1)
Frequency
●
●
●
●
V1, V2, V3 peak factor
●
●
●
I1, I2, I3 peak factor
●
●
●
U unbalance
●
●
●
V1, V2, V3, U12, U23, U31, I1, I2, I3, In
- Harmonics (2) of order 1 to 50
●
THD V1, V2, V3, U12, U23, U31, I1, I2,
I3
●
●
●
THD In
●
●
●
●
Hour meters: Network presence, on
charging, Uptime
●
Real energy Receiver, Generator
●
Reactive energy Q1, Q2, Q3, Q4
●
Apparent energy Receiver, Generator
●
Pulse counter input (0 to 8)
●
Analog input (0 to 8)
●
●
●
●
●
●
(1) Measured both in generator and receiver mode
(2) Up to order 25 for Enerium 100/110, Up to order 50 for Enerium 200/210/300/310