Variables
Range
Non-removable terminals
5 screw terminals for rigid and flexible cables of between 4 and 6 mm²
Maximum torque: 0.8 Nm
6.1.2 Current measurement inputs
6.1.2.1 Location
The current input terminals are labelled 1 to 5 on the rear right lower label.
6.1.2.2 Characteristics
Variables
Range
Starting current
5 mA
Normal input current
5 A
Maximum input current
6.5 A
Crest factor
3
Frequency
42.5 Hz to 69 Hz
24-hour overcurrent
10A
Short-term overcurrent
250 A, over 1s
Per-phase consumption
< 0.2 VA
Non-removable terminals
8 screw terminals for rigid and flexible cables of between 4 and 6 mm²
Maximum torque: 0.8 Nm
6.1.3 U and I protection
The use of fuses on the voltage inputs and a system for short-circuiting the input current is highly
recommended.
Current inputs