eNeRCo GRoUP, INC. |Indirect Fired Portable Heater

operating Instructions and owner’s Manual

trOuBlesHOOting

trOuBle

cause

sOlutiOn

The heater fails to start 

No power supply 

Check power specifications Check power con-
nections Check fuse 

Main switch in wrong position 

Select correct position 

Faulty operation of room thermostat 

Check thermostat position Check thermostat 
operation 

Air pressure switch tripped due to fan malfunc-
tion 

Check that the suction and the flow grills are 
unobstructed Check that the fan is running 
freely Check the electric motor and the con-
denser and, if faulty, replace them 

Air pressure switch tripped due to pressure 
switch malfunction 

Replace the pressure switch 

The heater stops and the warning 
light (1) comes on 

The ionisation electrode does not detect a 
flame 

Remove the flame sensor and clean it 

Safety thermostat tripped due to the combus-
tion chamber overheating 

Check that the suction and the flow grills are 
unobstructed Check that the room is well 
ventilated Check that the hot air can escape 
freely Check that the gas flow or pressure are 
not excessive 

Control unit tripped due to irregular burner 
operation 

Contact Service Assistance 

Faulty electronic control unit 

Check the unit and if necessary replace it. 

Faulty thermostat 

Check the thermostat and if necessary replace 
it 

The heater stops and then starts 
again 

Burner thermostat tripped 

Air distribution ducts too long or with   insuf-
ficient diameter 

Fan noise or vibrations 

Foreign bodies on fan blades 

Remove foreign bodies 

little air circulation 

eliminate all possible obstacles to proper air 
flow 

If heater still not working properly, please revert to nearest authorized dealer.

Содержание HeatStar 400IDG

Страница 1: ...251 0001 NATURAL GAS LPG FIRED HEATER heatstar BY eNERCO If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of li...

Страница 2: ...DERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTIONS MANUAL LABELS ETC CONTACT THE MANUFACTURER WARNING NOT FOR H...

Страница 3: ...page 5 and connected to an electrical switchboard When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at least 3 feet long and sufficient draft shall be cre...

Страница 4: ...ut Plug in the power cord having read the rating plate that specify electric supply characteristics Connect accessories such as the room thermostat or clock to the unit s control panel with the thermo...

Страница 5: ...ime is electronically set by a control flame box to lower the com bustion chamber temperature usually post ventilation lasts for 90 sec Warning Finally close the gas supply stopcock and turn of the se...

Страница 6: ...s on The ionisation electrode does not detect a flame Remove the flame sensor and clean it Safety thermostat tripped due to the combus tion chamber overheating Check that the suction and the flow gril...

Страница 7: ...type AWG 16 or AWG 18 wire or its equivalent as by here specified AP CONTROL BOX TA ROOM THERMOSTAT PLUG ST ELECTRIC PILOT LAMP FU FUSE LI1 OVERHEAT THERMOSTAT EV1 SOLENOID VALVE I Stage MB BURNER MO...

Страница 8: ...8 ENERCO GROUP INC Indirect Fired Portable Heater Operating Instructions and Owner s Manual 4000IDG Series Indirect Fired Heater...

Страница 9: ...508 Fuse holder 47 E10324 Fuse 6x30 25A 49 E20319 Terminal board 50 E20305 Terminal board 51 E10931 Transformer H T BRHAMA 52 E40229 Control box BRAHMA TGRD 81 120V 53 G06073 Plate for electrical comp...

Страница 10: ...sportation prepaid within said one year period and found by the Company to have imperfections in material or workmanship If a part is damaged or missing call our Technical Support Department at 800 25...

Отзывы: