operating Instructions and owner’s Manual

eNeRCo GRoUP, INC. |Indirect Fired Portable Heater

iMpOrtant

Before using the heater, read and understand all instructions and 
follow them carefully. The manufacturer is not responsible for 
damages to goods or persons due to improper use of units.

general recOMMendatiOns

This indirect-fired heater runs on natural gas or L.P.G. and is 
fitted with a flue to take the fumes away through the chimney.

Prior to shipping, the heater is configured for either natural gas 
or lP, labeled on the gas selector valve for the correct fuel type 
and given a complete functional test. To change the type of gas, 
follow the detailed instructions indicated in section “CHANGING 
TYPe oF GAS”. 

  Always follow local ordinances and codes when using this 

heater:

•  Read and follow this owner’s manual before using the 

heater.

•  Use only in places free of flammable vapors or high dust 

content.

•  Never use heater in immediate proximity of flammable 

materials (the minimum distance must be 6 ft.).

•  Make sure fire fighting equipment is readily available.
•  Make sure sufficient fresh outside air is provided according 

to the heater requirements. Direct combustion heaters 
should only be used in well vented areas in order to avoid 
carbon monoxide poisoning.

•  The heater is installed near a chimney to take away the 

fumes (see “Ventilation” on page 5) and connected to an 
electrical switchboard.

•  When the heater is connected to a flue pipe, the flue pipe 

shall terminate in a vertical section at least 3 feet long and 
sufficient draft shall be created to assure safe and proper 
operation of the heater.

•  Never block air inlet (rear) or air outlet (front).
•  In case of very low temperatures add kerosene to the 

heating oil.

•  Make sure heater is always under surveillance and keep 

children and animals away from it;

•  Before starting the heater always check free rotation of 

ventilator fan.

•  Indirect fired units only can be connected to air ducts to 

distribute warm air, with respect to the max. static pressure 
declared (see “TeCHNICAl SPeCIFICATIoN” sheet).

•  Unplug heater when not in use.

tecHnical speciFicatiOns

Hs 4000idg

Heat input

[kBTU/h]

380

Air flow

[cfm]

3,250

Heat output

[kBTU/h]

328.7

Natural Gas

Supply pressure

[in WC]

min 7’ w.c.

max 10” w.c.

Burner pressure

[in WC]

6.40

Fuel consumption

[CFH]

355.97

Position of gas selec-
tor value

lPG

Supply pressure

[in WC]

min 8’ w.c.

max 13’ w.c.

Burner pressure

[in WC]

7

Fuel consumption

[CFH]

133.89

Position of gas selec-
tor value

Power  
supply

Phase

1

Voltage

[V]

120

Frequency

[Hz]

60

electric consumption

[W]

1400

[A]

13.0

Adjustment of combustion air flap

[N]

3.0

Ring Nozzle

[in]

N. 12 holes x 

0.106”

Gas inlet connection thread

[psi]

3/4” HPT

Flue

[in]

5.91

Static pressure

[in]

0.60

Compulsory flue draft

[in]

0.05

Maximum air temperature

[°F]

250

Base unit

Dimensions, l x W x H

[in]

72.3 x 31.6 x 

30.4

Weight

[lb]

306

Packaging

Dimensions, l x W x H

[in]

74.1 x 26.0 x 

35.83

Weight

[lb]

361

           

Содержание HeatStar 400IDG

Страница 1: ...251 0001 NATURAL GAS LPG FIRED HEATER heatstar BY eNERCO If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of li...

Страница 2: ...DERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTIONS MANUAL LABELS ETC CONTACT THE MANUFACTURER WARNING NOT FOR H...

Страница 3: ...page 5 and connected to an electrical switchboard When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at least 3 feet long and sufficient draft shall be cre...

Страница 4: ...ut Plug in the power cord having read the rating plate that specify electric supply characteristics Connect accessories such as the room thermostat or clock to the unit s control panel with the thermo...

Страница 5: ...ime is electronically set by a control flame box to lower the com bustion chamber temperature usually post ventilation lasts for 90 sec Warning Finally close the gas supply stopcock and turn of the se...

Страница 6: ...s on The ionisation electrode does not detect a flame Remove the flame sensor and clean it Safety thermostat tripped due to the combus tion chamber overheating Check that the suction and the flow gril...

Страница 7: ...type AWG 16 or AWG 18 wire or its equivalent as by here specified AP CONTROL BOX TA ROOM THERMOSTAT PLUG ST ELECTRIC PILOT LAMP FU FUSE LI1 OVERHEAT THERMOSTAT EV1 SOLENOID VALVE I Stage MB BURNER MO...