POSITIONING AND INSTALLATION
The machine must only be installed outdoors. it is the user’s responsibility
to verify the need to provide protection with respect to atmospheric lightining
according to local legislation
The following must be taken into account when choosing the unit’s place of installation and making the
relative connections:
>
ambient temperature: 47°C maximum / minimum -20°C
>
maximum Humidity: 90%rH
>
avoid, in any way other objects to overlay unit
>
size and origin of the hydraulic piping;
>
location of the power supply;
>
accessibility for maintenance or repair operations;
>
solidity of the support surface;
>
ventilation of the air-cooled condenser;
>
orientation and exposure to solar radiation: keep the condensing coil out of direct sunlight whenever
possible;
>
do not position the unit in a way that strong winds favour air recirculation at the condensing coil;
>
do not position the machine on dark coloured land (e�g� tarred surfaces) so as not to cause functioning
overheating;
>
Verify that the installation is carried out only by qualified technical personnel and that they follow the
instructions in this manual and in compliance with the technical regulations;
>
Install the unit in locations accessible only by authorized personnel and provide for protection against
intrusion into the danger zone;
>
possible sound reverberation�
It is obligatory to observe the clearances specified in the dimensional drawing of the unit�
The unit must always be anchored to the ground�
Provide a solid base on which to position the unit� This support must be perfectly flat and horizontal� Its
dimensions must be suitable for those of the unit� This precaution is indispensable when the unit is to be
positioned on unstable ground (various lands, gardens etc�)�
Although the unit transmits low levels of vibrations to the supporting structure, it is advisable to lay a
sheet of hard rubber between the base of the unit and the supporting surface� If better insulation is
required, it is advisable to use the anti-vibration supports which are available as accessories�
In the event of installation on roofs or intermediate floors, the unit and the piping must be isolated from
the walls and ceilings� The units should not be positioned in proximity of private offices, bedrooms or
areas where low sound emissions are required� To prevent excessive sound reverberation, do not install
the unit in narrow or confined spaces�
The machine equipped with standard coils should not be installed in an environment where there is an
aggressive chemical atmosphere, in order to avoid the risk of corrosion�
Particular care should be taken to avoid atmospheres containing sodium chloride, which can aggravate
corrosion due to galvanic currents; a machine with untreated coils must not, for any reason, be installed
in a marine environment�
In the case of a marine or highly polluting industrial environment, it is necessary to request coils with
anti-corrosion surface treatment or copper-copper or copper-tinned copper coils�
In any case, please contact our commercial office to define the most suitable solution�