60
Troubleshooting
The engine starts but stops
again shortly afterwards
Fuel level too low
Top up with fuel
The fuel filter is clogged.
Replace the fuel filter.
Engine oil level too low (oil lack auto-
matic switch-off)
Bring the engine oil level up to
the maximum
Spark plug connector detached
Firmly put the spark plug con-
nector in place again
Tank vent on the tank cover is
blocked
Clean ventilation holes
The generator is running but
there is no voltage at the sock-
ets
Line circuit breaker has tripped out
(Pos.0)
Eliminate the cause and
switch the line circuit breaker
back on (Pos.1)
Insulation monitoring has tripped out Eliminate the cause and
switch the line circuit breaker
back on (Pos.1)
The alternator or cabling is defective Contact your service partner
The generator is running but
the output voltage is outside of
tolerance
The engine speed regulator is wrong-
ly adjusted or defective
Contact your service partner
The electronic voltage regulator is
wrongly adjusted or defective
Contact your service partner
The load from the connected con-
sumers is too high
Reduce the number of con-
sumers or their load
The power output remains sig-
nificantly below the nominal
output
Operation under extreme climatic
conditions
Adapt the usage for the climat-
ic conditions or terminate it
The generator has been poorly ser-
viced
Perform maintenance work
The generator has exceeded its wear
limit
Contact your service partner
The engine smokes
The engine oil level is too high
Draining off excess engine oil
The air filter insert (paper) is dirty or
contaminated with oil
Clean or replace the air filter
insert (always replace if oiled)
The air filter insert (foam) is dirty
Clean the air filter insert and
re-oil it
The generator is running with
distinct speed and voltage
fluctuations
The engine speed regulator is defec-
tive,
the carburettor is wrongly adjusted or
defective,
ECOtronic is defective
Contact your service partner
Malfunction