39
Commissioning
Your generator is designed for mobile use and according to the protective mea-
sure
.
DANGER!
Risk of dangerous contact voltages occurring when several consumers are
used from a single generator.
Risk of electric shock with life-threatening or fatal consequences.
► You must comply with the following instructions for connecting up the con-
sumables.
► Call in an electrician if necessary.
The above-mentioned safety standard differentiates between commissioning by
a qualified electrician and commissioning by an untrained person. There are two
options available for the untrained person:
1)
connection of a single piece of equipment to the generator
In this case it is not necessary to check the electrical safety (see Chapter
“Electrical safety“ in the operating instructions) beyond the protective mea-
sures. The protective conductor of the ground contact socket assumes the
function of the potential equalisation line.
This case expressly excludes
use of a power distributor (multiple socket).
2)
connection of one or more pieces of equipment to the generator
In this case the above-mentioned standard requires one of the following ad-
ditional protective measures:
a) protective separation with an insulation monitoring device (IMD) and au-
tomatic shut-off
b) Protective separation using a residual current protective (RCD) and au-
tomatic switching off. An
RCD or PRCD must be used for
each socket
or power circuit. We recommend that an RCD type B is used for 3-phase
networks.
IMPORTANT INFORMATION
REGARDING
THE CONNECTING UP
OF CONSUMERS
Protective separation with potential equalisation
designed according to DIN VDE 0100-551:2017-02 (HD 60364-5-551 +
A11:2016-05)