Technical data
RN22
20
Hauser
12.5 Performance characteristics
Response time
Step response (10 to 90 %)
≤ 1 ms
Step response (10 to 90 %) signal doubler output 2
HART filter
≤ 50 ms
Reference operating
conditions
• Calibration temperature: +25 °C ±3 K (77 °F ±5.4 °F)
• Supply voltage: 24 V
DC
/ 230 V
AC
• Output load: 225 Ω
• External output voltage (passive output): 20 V
DC
• Warm-up: > 1 h
Maximum measured error
Accuracies
Transmission error
< 0.1 % / of full scale value (< 20 µA)
Temperature coefficient
< 0.01 % /K
Long-term drift
Max. ±0.1 %/year (of full scale value)
12.6 Installation
Mounting location
The device is designed for installation on 35 mm (1.38 in) DIN rails in accordance with IEC
60715 (TH35).
NOTICE
‣
When using in hazardous areas, the limit values of the certificates and approvals must
be observed.
For information on ambient conditions, see the "Technical data" section.
Installing a DIN rail device
The device can be installed in any position (horizontal or vertical) on the DIN rail without
lateral clearance from neighboring devices. No tools are required for installation. The use
of end brackets (type "WEW 35/1" or similar) on the DIN rail is recommended to fix the
device.
If several devices are installed side by side, it is important to ensure that the
maximum side wall temperature of 85 °C (185 °F) is not exceeded. If this cannot be
guaranteed, mount the devices at a distance from one another or ensure sufficient
cooling.