Technical data
RN22
16
Hauser
11.2 Spare parts
Spare parts currently available for the device can be found online at:
http://www.products.endress.com/spareparts_consumables
. Always quote the serial
number of the device when ordering spare parts!
Type
Order code
Plug-in terminal set, 2-pin, DIN rail interfaces - screw
71505292
Plug-in terminal set, 2-pin, DIN rail interfaces - push-in
71505320
Front cover 12.5 mm, DIN rail housing (5 pcs per pack)
71505347
11.3 Return
The requirements for safe device return can vary depending on the device type and
national legislation.
1. Refer to the website for more information:
http://www.endress.com/support/return-material
2. Return the device if repairs or a factory calibration are required, or if the wrong
device was ordered or delivered.
11.4 Disposal
If required by the Directive 2012/19/EU on waste electrical and electronic equipment
(WEEE), the product is marked with the depicted symbol in order to minimize the
disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this
marking as unsorted municipal waste. Instead, return them to the manufacturer for
disposal under the applicable conditions.
12
Technical data
12.1 Function and system design
Product description RN22
Product design
Active barrier, 1-channel
• The active barrier is used for the transmission and galvanic isolation of 0/4 to 20 mA
signals. The device has an active/passive current input to which a 2- or 4-wire
transmitter can be directly connected. The output of the device can be operated actively
or passively. The current signal is then available to the PLC / controller or to other
instrumentation at plug-in screw terminals or optional push-in terminals.
• HART communication signals are transmitted bidirectionally by the device. Connecting
points for connecting HART communicators are integrated into the front of the device.
• The device is optionally available as an "associated apparatus", which allows devices to be
connected in Ex Zone 0/20 [ia] and operated in Ex Zone 2 [ec]. 2-wire transmitters are
supplied with power, and transmit analog 0/4 to 20 mA measured values from the
hazardous area to the non-hazardous area. These devices are accompanied by separate
Ex documentation, which is an integral part of this manual. Compliance with the
installation instructions and connection data in this documentation is mandatory!