RIA452
Commissioning
Hauser
117
Sw. delay
0..99
0
The starting time for 24-hour counting can be selected
with Sw. delay. Every time the instrument is reset, the
process of measuring 24 hours and the delay time is
restarted.
Example see Page 44
Sw. period
0..999
0
Limit value is activated cyclically every 24 hours for 0
to 999 seconds. The activation is delayed by [Sw.delay]
hours by changing the hour value (example
see Page 44).
Runtime
Displays the run time of the connected device, e.g.
pump, in hours [h].
Count
Records the switching frequency of the limit value.
Reset
No
Yes
Resets the run time and switching frequency for this
limit value.
Simu relay
Off
Low
High
Simulation of the selected limit value. Is automatically
set to
Off
when the menu item is exited.
Function
(menu
item)
Parameter setting
Description