RIA452
Commissioning
Hauser
107
Curve
Linear
Quad.
°C
°F
Kelvin
Linear or quadratic (quad.) characteristic of the sensor
used. Can be selected for analog signals. °C, °F, Kelvin
physical measured variable, can be selected for
temperature sensors.
Damp
0..99.9
0
Signal damping of measuring input with 1st order low
pass. Time constant can be selected from 0 to 99.9 sec.
Dimension
XXXXXXXXX
%
The technical unit or an arbitrary text for the measured
value of the sensor can be configured here. Max. length
9 characters.
Dec. point
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Number of places after the decimal point for displaying
the measured value.
0% value
-99999..99999
0
Start value of measured value, can be selected for
analog signal types
100% value
-99999..99999
100.0
End value of measured value, can be selected for analog
signal types
Offset
-99999..99999
0.0
Shifts the zero point of the response curve. This
function is used to adjust the sensor.
Comp. temp
Intern
const
Comparative temperature for thermocouple
measurement. An internal cold junction (= Intern) or a
constant value (= const) can be selected.
Const. temp
9999.9
20.0
Fixed comparative temperature.
This can only be selected if const is set for "Cmp.
Temp".
Open circ.
No
Yes
Switch cable open circuit detection for thermocouples
off or on
Function
(menu
item)
Parameter setting
Description