Electrical connection
Hauser
37
6
Electrical connection
6.1
NMT81 (Ex ia) intrinsically safe connection
NMT81, which uses intrinsically safe HART communication, must be connected to the
device's intrinsically safe terminal. Refer to the intrinsic safety regulations for establishing
wiring and field device layout.
1
2
3
5
6
4
A0042752
32
NMT81 terminal (ATEX
・
Ex ia)
1
Dummy plug
2
+ terminal (see Information)
3
- terminal (see Information)
4
Internal ground terminal for the cable shield
5
External ground terminal
6
Shielded twisted pair wire or steel-armored wire
• Only a metal cable gland may be used. The shielded wire on the HART
communication line must be grounded.
• The plug is also mounted at the side of [6] in the figure above prior to shipping. The
material of plug (aluminum or 316L) varies depending on the type of the
transmitter housing material.
Connection table
Connection to NRF590
Connection to NMS5
Connection to NMS8x/NMR8x/NRF81
+ Terminal
24, 26, 28
+ Terminal
24
+ Terminal
E1
- Terminal
25, 27, 29
- Terminal
25
- Terminal
E2
1)
If an analog Ex i/IS 4 to 20 mA HART module is installed, NMT81 can be connected to slot B2, B3 or C2,
C3.