Mounting
5.1
Mounting requirements
5.1.1
Installation conditions for sensor for level measurements
3
4
1
5
6
D
r
7
1
6
/ !
2
!
A0038210
1
Installation conditions
1
Distance to vessel wall: ¹⁄₆ of vessel diameter
2
Use of a weather protection cover; protection from direct sunlight or rain
3
Do not install the sensor in the middle of the vessel.
4
Avoid measurements through the filling curtain.
5
Do not install limit switches or temperature sensors inside the beam angle.
6
Measurement is affected by symmetrical fittings, e.g. heating coils and baffles.
7
Position the sensor so that it is perpendicular to the product surface.
• Install only one device per vessel: signals from multiple devices will interfere with each
other.
• Determine the detection range using a 3 dB beam angle α.
Further information is available in the Operating Instructions.
5.1.2
Installation conditions for the sensor for flow measurements
• Mount the measuring device on the upstream side immediately above the maximum upper
water level H
max
• Take the blocking distance into account
• Position the measuring device in the center of the flume or weir