Proline t-mass 65F, 65I
8
Hauser
Power supply
Electrical connection
measuring unit
a0005135
Connecting the transmitter, cable cross-section: max. 2.5 mm
2
(AWG 13)
A
View X (field housing)
B
View Y (wall-mount housing)
*)
Not available yet (left in deliberately)
a
Cover of the connection compartment
b
Cable for power supply: 85 to 260 V AC, 20 to 55 V AC,16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L– for DC
c
Ground terminal for protective conductor
d
Signal cable: See Terminal assignment
→
Page 7
Fieldbus cable:
Terminal Nr. 26: PROFIBUS DP / MODBUS RS485
→
A (RxD/TxD-P)
Terminal Nr. 27: PROFIBUS DP / MODBUS RS485
→
B (RxD/TxD-N)
e
Ground terminal for signal-cable shield / RS485 line
Observe that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
(max. 5 mm)
f
Service connector for connecting service interface FXA193 (Fieldcheck, Tof Tool - Fieldtool)
g
Signal cable: See Terminal assignment
→
Page 7
PROFIBUS cable for external termination, optional:
Terminal No. 24: +5 V
Terminal No. 25: DGND
MODBUS RS485 cable for status input:
Terminal No. 24: 3 to 30 V DC, R
ι
= 3 k
Ω
Terminal No. 25: GND
a
a
HART
MODBUS RS485
PROFIBUS PA*
FOUNDA
TION Fieldbus*
27
25
23
21
2
1
26
24
22
20
L1 (L+)
N (L-)
–
–
–
+
+
+
B (RS485)
A (RS485)
d
c
e
b
– 27
– 25
– 23
– 21
+ 26
+ 24
+ 22
+ 20
N (L-) 2
L1 (L+)1
25
23
21
2
1
24
22
20
L1 (L+)
N (L-)
–
–
–
+
+
+
27
26
X
Y
d
b
g
d
c
e
b
g
d
c
e
b
g
PROFIBUS DP
(d)
b d/(g)
f
f
f
B (RS485)
A (RS485)
Esc
E
-
+
Esc
E
-
+