Proline Prosonic Flow 93 PROFIBUS DP/PA
Commissioning
Hauser
99
8.
Select the operating mode:
Select the operating mode (GSD file) which should be used for cyclic communication with the
PROFIBUS master (Class 1).
BASIC FUNCTION (G)
→
PROFIBUS DP (GBA)
→
OPERATION (614)
→
SELECTION GSD (6140)
→
Options:
– MANUFACT. SPEC. (factory setting): the complete device functionality is available.
– PROFILE GSD: Prosonic Flow 93 is operated in the PROFIBUS Profile mode.
!
Note!
For PROFIBUS network configuration, make sure that the right device master file (GSD file) of
the measuring device is used for the selected operating mode
9.
Configuration of cyclic data transmission in the PROFIBUS master
A detailed description of the system integration can be found on
6.4.2
PROFIBUS PA commissioning
The following steps must be carried out in the sequence specified:
1.
Check the hardware write protection:
The WRITE PROTECT (6102) parameter indicates whether it is possible to write to the device
functions via PROFIBUS (acyclic data transmission, e.g. via the operating program "FieldCare").
!
Note!
This check is not needed if operating via the local display.
BASIC FUNCTION (G)
→
PROFIBUS PA (GCA)
→
CONFIGURATION (610)
→
WRITE PROTECT (6102)
→
Display of one of the following options:
– OFF (factory setting) = write access via PROFIBUS possible
– ON = write access via PROFIBUS not possible
Deactivate the write protection if necessary
2.
Enter the tag name (optional):
BASIC FUNCTION (G)
→
PROFIBUS PA (GCA)
→
CONFIGURATION(610)
→
TAG NAME (6100)
3.
Configuring the fieldbus address:
Software addressing using the local display or an operating program:
BASIC FUNCTION (G)
→
PROFIBUS PA (GCA)
→
CONFIGURATION (610)
→
FIELDBUS ADDRESS (6101)
Hardware addressing via miniature switches
4.
Select the system unit:
a. Determine the units by means of the system units group:
MEASURED VARIABLES (A)
→
SYSTEM UNITS (ACA)
→
CONFIGURATION (040)
→
UNIT MASS FLOW (0400) / UNIT MASS (0401) / UNIT
VOLUME FLOW (0402) / …
b. In the function UNIT TO BUS (6141), select the option SET UNITS, so that the measured
variables transmitted cyclically to the PROFIBUS master (Class 1) are transmitted with the
system units set in the measuring device:
BASIC FUNCTION (G)
→
PROFIBUS PA (GCA)
→
OPERATION (614)
→
UNIT TO BUS )