System integration
Proline Promass F 100 Modbus RS485
50
Scan list configuration
For configuration, the Modbus RS485 register addresses of the device parameters to be
grouped must be entered in the scan list. Please note the following basic requirements of
the scan list:
Max. entries
16 device parameters
Supported device parameters
Only parameters with the following characteristics are supported:
• Access type: read or write access
• Data type: float or integer
Configuring the scan list via FieldCare or DeviceCare
Carried out using the operating menu of the measuring device:
Expert → Communication → Modbus data map → Scan list register 0 to 15
Scan list
No.
Configuration register
0
Scan list register 0
...
...
15
Scan list register 15
Configuring the scan list via Modbus RS485
Carried out using register addresses 5001 - 5016
Scan list
No.
Modbus RS485 register
Data type
Configuration register
0
5001
Integer
Scan list register 0
...
...
Integer
...
15
5016
Integer
Scan list register 15
Reading out data via Modbus RS485
The Modbus master accesses the data area of the Modbus data map to read out the current
values of the device parameters defined in the scan list.
Master access to data area
Via register addresses 5051-5081
Data area
Device parameter value
Modbus RS485 register
Data type*
Access**
Start register
End register
(Float only)
Value of scan list register 0
5051
5052
Integer/float
Read/write
Value of scan list register 1
5053
5054
Integer/float
Read/write
*
Data type depends on the device parameters entered in the scan list.
**
Data access depends on the device parameters entered in the scan list. If the device parameter entered
supports read and write access, the parameter can also be accessed via the data area.