Technical data
Proline Promass F 100 Modbus RS485
102
DN
1:1
1:10
1:20
1:50
1:100
1:500
[inch]
[lb/min]
[lb/min]
[lb/min]
[lb/min]
[lb/min]
[lb/min]
6
29
400
2
940
1
470
588
294
58.80
10
80
850
8
085
4
043
1
617
808.5
161.7
Accuracy of outputs
The output accuracy must be factored into the measured error if analog outputs are
used, but can be ignored for fieldbus outputs (e.g. Modbus RS485, EtherNet/IP).
The outputs have the following base accuracy specifications.
Repeatability
o.r. = of reading; 1 g/cm
3
= 1 kg/l; T = medium temperature
Base repeatability
Design fundamentals → 104
Mass flow and volume flow (liquids)
±0.025 % o.r. (PremiumCal, for mass flow)
±0.05 % o.r.
Mass flow (gases)
±0.25 % o.r.
Density (liquids)
±0.00025 g/cm
3
Temperature
±0.25 °C ± 0.0025 · T °C (±0.45 °F ± 0.0015 · (T–32) °F)
Response time
The response time depends on the configuration (damping).
Influence of ambient
temperature
Current output
o.r. = of reading
Temperature coefficient
Max. ±0.005 % o.r./°C
Pulse/frequency output
Temperature coefficient
No additional effect. Included in accuracy.
Influence of medium
temperature
Mass flow and volume flow
o.f.s. = of full scale value
When there is a difference between the temperature for zero point adjustment and the
process temperature, the additional measured error of the sensor is typically ±0.0002 %
o.f.s./°C (±0.0001 % o. f.s./°F).