Commissioning
Proline Promass 80
22
Hauser
5.5 Software settings
5.5.1 Device address
Has to be set for measuring devices with the following communication methods:
• PROFIBUS PA
Device address range: 0 to 126, factory setting 126
The device address can be configured via:
• Miniature switches
→
see section Hardware settings
→
16
• Local operation
→
see description below
Note! The Commissioning Quick Setup has to be executed before setting the device address.
1.
F
→
Enter the function matrix
2.
P
→
Select the COMMUNICATION group
F
→
Con
fi
rm selection
3.
N
→
Select the BUS ADDRESS function
4.
P
→
Enter the desired device address
F
→
Con
fi
rm entry
5.
P
→
> 3 s = Return to the measured value display