Operating conditions: Installations
Installation instructions
Mounting location
Entrained air or gas bubble formation in the measuring tube can result in an increase in measuring errors.
Avoid
the following installation locations in the pipe:
• Highest point of a pipeline. Risk of air accumulating!
• Directly upstream from a free pipe outlet in a vertical pipeline.
A0011899
Mounting location
Installation of pumps
Sensors may not be installed on the pump suction side. This precaution is to avoid low pressure and the
consequent risk of damage to the lining of the measuring tube. Information on the pressure tightness of the
measuring tube lining
19, Section "Pressure tightness".
Pulsation dampers may be needed when using piston pumps, piston diaphragm pumps or hose pumps.
Information on the shock and vibration resistance of the measuring system
18, Section "Shock and
vibration resistance".
A0011900
Installation of pumps
h
2 x DN
³