Description of device parameters
Proline Promag 300 Modbus RS485
206
Hauser
Additional information
Dependency
The input range is dependent on the option selected in the
Current span
parameter
FreqOutputSim 1 to n
Navigation
Expert → Diagnostics → Simulation → FreqOutputSim 1 to n (0472–1 to n)
Prerequisite
In the
Operating mode
Frequency
option is selected.
Description
Use this function to switch simulation of the frequency output on and off. The display
alternates between the measured value and a diagnostic message of the "Function check"
category (C) while simulation is in progress.
Selection
• Off
• On
Factory setting
Off
Additional information
Description
The desired simulation value is defined in the
Freq value 1 to n
parameter.
Selection
• Off
Frequency simulation is switched off. The device is in normal measuring mode or
another process variable is being simulated.
• On
Frequency simulation is active.
Freq value 1 to n
Navigation
Expert → Diagnostics → Simulation → Freq value 1 to n (0473–1 to n)
Prerequisite
In the
FreqOutputSim 1 to n
parameter, the
On
option is selected.
Description
Use this function to enter a frequency value for the simulation. In this way, users can verify
the correct adjustment of the frequency output and the correct function of downstream
switching units.
User entry
0.0 to 12
500.0 Hz