Proline Promag 300 Modbus RS485
Description of device parameters
Hauser
123
Pulse width
Navigation
Expert → Output → PFS output 1 to n → Pulse width (0452–1 to n)
Prerequisite
In the
Operating mode
Pulse
option is selected, and one of
the following options is selected in the
Assign pulse
• Mass flow
• Volume flow
• Correct.vol.flow
Description
Use this function to enter the duration of the output pulse.
User entry
0.05 to 2
000 ms
Factory setting
100 ms
Additional information
Description
• Define how long a pulse is (duration).
• The maximum pulse rate is defined by f
max
= 1 / (2 × pulse width).
• The interval between two pulses lasts at least as long as the set pulse width.
• The maximum flow is defined by Q
max
= f
max
× pulse value.
• If the flow exceeds these limit values, the measuring device displays the diagnostic
message
S443 Pulse output 1 to n
.
B = P
B
P
P
B
B < P
t
t
U[V]
U[V]
A0026882
B
Pulse width entered
P
Pauses between the individual pulses
Example
• Pulse value: 0.1 g
• Pulse width: 0.1 ms
• f
max
: 1 / (2 × 0.1 ms) = 5 kHz
• Q
max
: 5 kHz × 0.1 g = 0.5 kg/s
Measuring mode
Navigation
Expert → Output → PFS output 1 to n → Measuring mode (0457–1 to n)
Prerequisite
In the
Operating mode
Pulse
option is selected and in the
Assign pulse
parameter (→ 122) one of the following options is selected:
• Mass flow
• Volume flow
• Correct.vol.flow