Electrical connection
Proline 300 Modbus RS485
16
Hauser
Standard cable - customer-specific cable
No cable is supplied, and it must be provided by the customer (up to max. 300 m (1
000 ft))
for the following order option:
Order code for DKX001: Order code
040
for "Cable", option
1
"None, provided by customer, max
300 m"
A standard cable can be used as the connecting cable.
Standard cable
4 cores (2 pairs); pair-stranded with common shield
Shielding
Tin-plated copper-braid, optical cover ≥ 85 %
Capacitance: core/shield
Maximum 1
000 nF for Zone 1, Class I, Division 1
L/R
Maximum 24 µH/Ω for Zone 1, Class I, Division 1
Cross-section
Max. cable length for use in
Non-hazardous area,
Ex Zone 2, Class I, Division 2
Ex Zone 1, Class I, Division 1
0.34 mm
2
(22 AWG)
80 m (270 ft)
0.50 mm
2
(20 AWG)
120 m (400 ft)
0.75 mm
2
(18 AWG)
180 m (600 ft)
1.00 mm
2
(17 AWG)
240 m (800 ft)
1.50 mm
2
(15 AWG)
300 m (1
000 ft)
Содержание Proline 300
Страница 34: ......
Страница 35: ......
Страница 36: ...www addresses endress com 71528708 71528708 ...