Picomag IO-Link
Electrical connection
Hauser
19
Internal resistance: 7.5 kΩ
IO-Link configuration version
Option only available for output 1 in the
→ 24 submenu
The measuring device features an IO-Link communication interface with a baud rate of
38,400 and with a second IO function on pin 2. This requires an IO-Link compatible
module (IO-Link master) for operation. The IO-Link communication interface allows direct
access to the process and diagnostics data.
6.3
Connecting the measuring device
NOTICE
The measuring device may only be installed by properly trained technicians.
‣
Comply with national and international regulations regarding the installation of
electrotechnical systems.
‣
Power supply according to EN 50178, SELV, PELV or Class 2.
1. De-energize the system.
2. Connect the measuring device via the connector.
3.
1
A0046190
1
Ground terminal
In the case of non-grounded pipes:
The device must be grounded using the ground terminal accessory.
6.4
Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables have adequate strain relief?
Is the connector connected correctly?
Does the supply voltage match the specifications on the measuring device?
Is the pin assignment of the connector correct?
Is the potential equalization established correctly?