Commissioning
Picomag IO-Link
24
Hauser
9.3.4
Configuring the IO modules
The measuring device has two signal inputs or signal outputs that can be configured
independently of one another:
• Pulse output → 25
Navigation
Menu: "Guidance" → Output 1
Menu: "Guidance" → Output 2
Parameter overview with brief description
Parameter
Description
Selection
Factory setting
Output 1
Select the operating mode of output 1.
• Pulse output
• Current output
• Switch output
• Voltage output
• Digital input
• IO-Link
• Off
IO-Link
Output 2
Select the operating mode of output 2.
• Current output
• Switch output
• Voltage output
• Digital input
• Off
Off
Configuring the current output
The Current output submenu contains all the parameters that must be configured for the
configuration of the current output.
The output is used to output process variables by analog means in the form of a 4-20 mA
current.
Navigation
Menu: "Guidance" → Output 1 → Current output
Menu: "Guidance" → Output 2 → Current output
Parameter overview with brief description
Parameter
Description
Selection/input
Factory setting
Assign current output
Select process variable for current output.
• Off
• Volume flow
• Temperature
• Conductivity
Volume flow
4 mA value
Enter 4 mA value.
Floating point number with sign
0 l/min
20 mA value
Enter 20 mA value.
Floating point number with sign
Depends on the nominal diameter:
DN 15 (½"): 25 l/min (6.6 gal/min)
DN 20 (¾"): 50 l/min (13.2 gal/min)
DN 25 (1"): 100 l/min (26.4 gal/min)
DN 50 (2"): 750 l/min (198.1 gal/min)