Trouble-shooting
Fault
Reason Remedy
Does not switcht No power
(green LED does not light up)
Check power
Elektronik defekt
Replace FTL 325 P
Contacts welded together
(after short-circuit)
Replace FTL 325 P;
connect a fuse into contactor
circuit
Measuring transmitter
defective
Replace measuring transmitter
Switches
incorrectly
Incorrect setting of
change-over switch for
limit signal in FTL 325 P
Correctly set change-over
switch behind front panel
(p. 15…19)
Permanent
alarm signal
Interrupt or short-circuit line to
measuring transmitter
Check line
Measuring transmitter
electronics defective
Replace measuring transmitter
electronics
Switches
incorrectly after
power failure
FEL 57,
Behaviour during switch-on
test
(functional test)
Observe switching behaviour
of FEL 57;
after power failure block plant
control for up to 45 s