Electrical Connection

For the AC version, two wires are required (

L

L1

1

N

N

), while

for the DC version, three wires (

L

L+

+

L

L--

,

  P

PN

NP

P

). The DC

version has an integrated protection against reversed
polarity and short-circuit.
A ground connection (PE) is required for the dust-Ex
version FTC 968 Z only, as the Nivector is an insulation
covered instrument of the type Protection Class II.

The AC version of the Nivector may only be connected to
the power supply when an external load is connected to
it! 

A check must be made to ensure that the stated limits are
not exceeded when instruments are connected (see
Electrical Data, Page 8). Exceeding the load limits and
short-circuiting will permanently damage the limit switch!
With small voltage supplies, take into account the voltage
drop between the external load and the Nivector.
When the electronic switch of the Nivector is open, a
small no-load current will still flow. This means that any
instruments connected are not separated from the power
supply (see Technical Data).

W

Wiirriin

ng

g

Lift the clip of the connecting cap with a screwdriver and
remove cap 

Pull the cable through both the cable gland and the
connection cap

Wire up the Nivector as shown in the connection diagram

Push on the connecting cap until the clip catches

Tighten cable gland

C

Co

on

nn

ne

ec

cttiio

on

n

d

diia

ag

grra

am

m    

Connection cap

Cable gland

Clip

Fig. 6
Lift off connection cap

Fig. 7
Left:
AC version

Right:
DC version

4

Содержание nivector FTC 968

Страница 1: ...s unterer Grenzstandschalter Dauerber hrung mit dem F ll gut hat S St ta au ub b E Ex x V Ve er rs si io on n Die Ausf hrung Nivector FTC 968 Z ist einsetzbar im staubexplosionsgef hrdeten Bereich Zon...

Страница 2: ...vem Me system Ber hrt F llgut die Stirnfl che bet tigt die Me elektronik einen elektronischen Schalter Thyristor bzw Transistor Die Schirmelektrode verhindert Einfl sse durch seitliche Ansatzbildung o...

Страница 3: ...Ka beldurchf hrung kann in jede beliebige Richtung gedreht werden Bei der Montage das Kunststoffgewinde nicht berdrehen Abb 3 links Standardeinbau rechts Einbau bei Ansatzbil dung an der Beh lter wan...

Страница 4: ...t berschrei tung und Lastkurzschlu zerst ren den Grenzschalter Bei kleinen Netzspannungen mu der Spannungsabfall ber der externen Last und ber dem Nivector ber ck sichtigt werden Wenn der elektronisch...

Страница 5: ...renzschalter auf Minimum Sicherheit eingestellt werden Mit einem Schraubendreher wird der M MI IN N M MA AX X Schalter im Anschlu raum des Nivectors in die entsprechende Position gebracht siehe Abb 2...

Страница 6: ...ta an nd d v ve er rk kl le ei in ne er rn n Der MIN MAX Schalter am Nivector mu auf MIN Posi tion stehen die LED mu leuchten leuchtet die LED nicht Potentiometer f r Empfindlichkeit so weit ent gege...

Страница 7: ...g max 6 bar T Te em mp pe er ra at tu ur r Umgebungstemperatur anschlu seitig 20 C 60 C Betriebstemperatur beh lterseitig 20 C 80 C FTC 968 Z Betriebstemperatur beh lterseitig 20 C 75 C F F l ll lg gu...

Страница 8: ...375 VA 253 V bzw Pmax 36 VA 21 V G Gl le ei ic ch hs st tr ro om m a au us sf f h hr ru un ng g Dreileiteranschlu Lastanschlu open collector PNP Versorgungsspannung 10 V 55 V Stromaufnahme max 15 mA S...

Страница 9: ...out if the Nivector is used as the lower limit switch and is in permanent contact with the material D Du us st t E Ex x V Ve er rs si io on n The Nivector FTC 968 Z version can be used in dust explosi...

Страница 10: ...measuring system When solids touch the sensor tip then the measuring electronics activate an electronic switch thyristor or transistor The surface protective electrode prevents influences such as tho...

Страница 11: ...nting do not overtighten the plastic thread Bush G1 Fig 3 Left standard application Right mounted for build up when on vessel wall occurs Bush G1 Bush G11 2 Fig 4 Left mounted in the Protector to prot...

Страница 12: ...ceeding the load limits and short circuiting will permanently damage the limit switch With small voltage supplies take into account the voltage drop between the external load and the Nivector When the...

Страница 13: ...ed as a lower limit switch or the other way round The M MI IN N M MA AX X switch in the connection area of the Nivector is set with a screwdriver see Fig 2 Page 2 M Ma ax xi im mu um m F Fa ai il l S...

Страница 14: ...ta an nc ce e The MIN MAX switch on the Nivector must be in the MIN position and the LED must be lit If the LED is not lit then turn the sensitivity potentiometer counterclockwise until the LED light...

Страница 15: ...ur re e Ambient temperature connection 20 C 60 C operating temperature vessel 20 C 80 C FTC 968 Z operating temperature vessel 20 C 75 C P Pr ro od du uc ct t Grain size 0 10 mm dielectric constant r...

Страница 16: ...oltage drop across switching transistor operating with load max 3 V residual current 100 A Connecting external load Imax 350 mA transient 50 ms Imax 550 mA Short circuit protection Accessories Protect...

Отзывы: