Operating menu
Micropilot FMR51, FMR52 FOUNDATION Fieldbus
128
Hauser
User entry
Depending on the antenna
Factory setting
Depending on the antenna
Additional information
0%
E
A0019486
27
Empty calibration (E) for level measurements in liquids
The measuring range starts at the point at which the radar beam hits the tank or silo
bottom. In the case of dished boiler ends or conical outlets levels below this point can
not be measured.
Full calibration
Navigation
Setup → Full calibr.
Description
Specify the distance F between the minimum level (0%) and the maximum level (100%).
User entry
Depending on the antenna
Factory setting
Depending on the antenna
Additional information
0%
F
100%
A0019487
28
Full calibration (F) for level measurements in liquids