Liquiphant S FTL70, FTL71
13
Switching behavior of the connected device:
Please note this switching response and function of the plant especially when replacing a
Liquiphant with an EL17Z or FEL37 electronic insert using a Liquiphant S with FEL57 electronic insert.
Output signal
Signal on alarm
Output signal on power failure or in the event of damaged sensor: 0 Hz
Connectable load
• Floating relay contacts in the connected switching device Nivotester FTL320, FTL325P,
FTL370, FTL372, FTL375P
• For contact load, see the Technical Data of the switching unit.
L00-FTL5xxxx-05-05-xx-en-000
* De-energized on power supply failure
Fail-safe mode
set at
switching unit
Max.
Max.
Max.
Max.
Min.
Min.
Min.
Min.
Setting
at FEL57
STD
EXT
STD
EXT
STD
EXT
STD
EXT
Fork
free
free
covered
covered
free
free
covered
covered
Switching status of relay in switching unit
on = energised
off = de-energised
Test start
End of test start
(power off)
(power on)
> 3 s
on
on
off
off
off
off
on
on
off
off
off
off
~ 3 s on
~ 3 s on
~ 3 s on
~ 3 s on
~ 5 s off
~ 5 s off
off
off
~ 5 s off
~ 7 s off
~ 5 s off
~ 5 s off
~ 2 s on
~ 2 s on
~ 3 s on
on
~ 35 s on
~ 3 s off
~ 2 s off
~ 35 s off
off
~ 30 s on
on
on
on
off
*
*
*
*
Safety mode
Level
Output signal
(PFM)
LEDs
green
yellow
L00-FTL5xxxx-07-05-
xx-xx-000
= lit
= unlit
L00-FTL5xxxx-04-05-xx-xx-008
150 Hz
50 Hz