Levelflex FMP53 PROFIBUS PA
Integration into a PROFIBUS network
Hauser
25
8
Integration into a PROFIBUS network
8.1
Overview of the device database files (GSD)
Manufacturer ID
17 (0x11)
Ident number
0x1558
Profile version
3.02
GSD file
Information and files under:
•
www.endress.com
•
www.profibus.org
GSD file version
8.2
Set device address
2
98
3
4
5
6
7
8
1
D
IP
O
N
A0015686
8
Address switches in terminal compartment
8.2.1
Hardware adressing
1. Set switch 8 to "OFF".
2. Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts automatically.
Switch
1
2
3
4
5
6
7
Value in position "ON"
1
2
4
8
16
32
64
Value in position "OFF"
0
0
0
0
0
0
0