Levelflex FMP53 PROFIBUS PA
Electrical connection
Hauser
23
1. Loosen the screw of the securing clamp on the connection compartment cover and turn
the securing clamp 90° counterclockwise.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Remove the cable sheath.
5. Strip the cable ends over a length of 10 mm (0.4 in). In the case of stranded cables, also
fit ferrules.
6. Firmly tighten the cable glands.
7.
A0032468
Connect the cable in accordance with the terminal assignment → 18.
8. If using shielded cables: Connect the cable shield to the ground terminal.
9. Fit the cover of the connection compartment back on.
10. If present, turn the cover lock so that it is located over the edge of the cover and then
tighten.
7.2.1
Plug-in spring-force terminals
In the case of devices without integrated overvoltage protection, electrical connection is via
plug-in spring-force terminals. Rigid conductors or flexible conductors with ferrules can be
inserted directly into the terminal without using the lever, and create a contact automatically.