Liquiphant FTL62 with electronic insert FEL67
Declaration of Conformity
Hauser
5
1.1
Safety-related characteristic values
SIL_00351_01.20
General
Device designation and permissible types
Liquiphant with electronic insert FEL67
FTL62–**A7*************+LA
Safety-related output signal
For connection to dedicated Nivotester only
Fault signal
Process variable/function
Level switch for liquids
Safety function(s)
Overfill protection or operating maximum/minimum detection
Device type acc. to IEC 61508-2
Type A
Type B
Operating mode
Low Demand Mode
High Demand Mode
1)
Continuous Mode
Valid hardware version
01.00.ww (ww: any double number)
Valid so ware version
01.01.zz (zz: any double number)
Safety manual
FY01018F
Type of evalulation
(check only one box)
Complete HW/SW evaluation parallel to development incl.
FMEDA and change request acc. to IEC 61508-2, 3
Evaluation of “proven in use” performance for HW/SW incl. FMEDA
and change request acc. to IEC 61508-2, 3
Evaluation of HW/SW field data to verify „prior use” acc. to
IEC 61511
Evaluation by FMEDA acc. to IEC 61508-2 for devices w/o so ware
Evaluation through – report/certificate no.
TÜV Rheinland / 968/FSP 1388.02/20
Test documents
Development documents
Test reports
Data sheets
SIL - Integrity
Systematic safety integrity
SIL 2 capable
SIL 3 capable
Hardware safety integrity
Single channel use (HFT = 0)
SIL 2 capable
SIL 3 capable
Multi channel use (HFT
³
1)
SIL 2 capable
SIL 3 capable
FMEDA
Safety function
MIN
MAX
—
λ
DU
2),3)
28 FIT
13 FIT
—
λ
DD
2),3)
140 FIT
106 FIT
—
λ
SU
2),3)
133 FIT
149 FIT
—
λ
SD
2),3)
5 FIT
41 FIT
—
SFF
91%
96%
—
PFD
avg
(T
1
= 1 year)
3)
(single channel architecture)
1.24 × 10
-4
5.67× 10
-5
—
PFH
3)
2.83 × 10
-8
1/h
1.29 × 10
-8
1/h
—
PTC
4)
Test sequence A
94%
94%
—
Test sequence B
8%
17%
—
λ
total
2),3)
307 FIT
308 FIT
—
Diagnostic test interval
5)
≤
60 s, except RAM check
≤
10 min
—
Fault reaction time
6)
≤
3 s
—
Comments
Nivotester works without so ware.
Declaration
Our internal company quality management system ensures information on safety-related systematic faults which become evident
in the future
1)
Maximum admissible 1 demand per week.
2)
FIT = Failure In Time, number of failures per 10
9
h
3)
Valid for average ambient temperature up to +40 °C (+104 °F)
For continuous operation at ambient temperature close to +60 °C (+140 °F), a factor of 1.5 should be applied
4)
PTC = Proof Test Coverage
5)
All diagnostic functions are performed at least once within the diagnostic test interval
6)
Maximum time between error recognition and error response
A0042176