Gamma Modulator FHG65 Synchronizer FHG66

Hauser

7

Alarm output

The Gamma Modulator FHG65 does not have an alarm output of its own. Operating errors are

reported as follows:

If a Synchronizer FHG66 is connected:

 The FHG65 reports the error to the FHG66 via the

synchronization input. The alarm relay of the FHG66 reports the error.

If a Synchronizer FHG66 is not connected:

 The FHG65 switches off its motor completely in the

event of an error. This reduces the current consumption to less than 30 mA. This can be detected

by an external current monitor (e.g. Dold IK9076.11)

IK 9076.11

DC 24V

< 0.1 A

A1 +/i

DC 24V

11

k

L-

A2’-

14

12

A2-

L+

FHG65

0V

  A0018539

 1

Connection diagram for external current monitor Dold IK9076.11

Environment

Ambient temperature:

• Without water cooling: –40 to +60 °C (–40 to +140 °F)

• With water cooling at the water cooling jacket: 0 to +120 °C (32 to +248 °F)

• With water cooling at the terminal head: max. +75 °C (+167 °F)

Storage temperature:

 –40 to +75 °C (–40 to +167 °F)

Housing degree of protection:

 IP66/67; TYPE 4X/6

Climate class:

 DIN EN 60068-2-38 test Z/AD

Vibration resistance:

 DIN EN 60068-2-64 test Fh; 10 to 2

 

000 Hz, 1 (m/s

2

)

2

/Hz

Shock resistance:

 DIN EN 60068-2-27; test Ea; 30 g, 18 ms, 3 shocks /direction/axis

Electromagnetic compatibility:

 Interference emission according to EN 61326, Appendix A

(Industrial) and NAMUR Recommendation NE21

Interference suppression

FMG50

Max 5 µSv/h per 1

 

000 mm (39.4 in) measuring length:

• Measuring range 200 mm (7.87 in): 25 µSv/h max. interference suppression

• Measuring range 800 mm (31.5 in): 6 µSv/h max. interference suppression

• Measuring range 2

 

000 mm (78.7 in): 2.5 µSv/h max. interference suppression

• Measuring range 10

 

000 mm (394 in)- cascading: 0.5 µSv/h max. interference suppression

FMG60

Max 10 µSv/h per 1

 

000 mm (39.4 in) measuring length:

• Measuring range 200 mm (7.87 in): 50 µSv/h max. interference suppression

• Measuring range 800 mm (31.5 in): 12.5 µSv/h max. interference suppression

• Measuring range 2

 

000 mm (78.7 in): 5 µSv/h max. interference suppression

• Measuring range 10

 

000 mm (394 in)- cascading: 1 µSv/h max. interference suppression

Содержание FHG65

Страница 1: ...onization of an unlimited number of Gamma Modulators FHG65 and operating status display for easy diagnosis of the connected Modulators FHG65 Advantages Disturbance free measurement in the event of int...

Страница 2: ...on requirements 9 Mechanical construction 11 Ordering information 13 Synchronizer FHG66 14 Technical data 14 Electrical connection 15 Installation requirements 16 Mechanical construction 17 Human inte...

Страница 3: ...tive substances or ionizing radiation Permitted Procedures processes or actions that are permitted Preferred Procedures processes or actions that are preferred Forbidden Procedures processes or action...

Страница 4: ...occurring sporadically e g from nondestructive material testing Using a frequency filter the FMG50 or FMG60 can thus separate the useful signal from interference radiation In this way it is possible...

Страница 5: ...rly of its alarm output is recommended for minimum point level detection as an undetected failure of the Modulator FHG65 may result in faulty switching behavior 1 1 1 1 2 2 A B A0021133 A Maximum poin...

Страница 6: ...ther 3 2 SYNC1 SYNC3 CASC IN SYNC1 SYNC2 SYNC3 SYNC2 18 35 VDC 1 1 1 1 1 18 36 VDC 18 36 VDC 18 36 VDC 18 36 VDC 18 36 VDC A0018541 1 FHG65 2 Primary synchronizer 3 Cascaded synchronizer Gamma Modulat...

Страница 7: ...Storage temperature 40 to 75 C 40 to 167 F Housing degree of protection IP66 67 TYPE 4X 6 Climate class DIN EN 60068 2 38 test Z AD Vibration resistance DIN EN 60068 2 64 test Fh 10 to 2000 Hz 1 m s2...

Страница 8: ...nment L 1 L 2 3 4 18 36 VDC SYNC IN A B L 1 L 2 3 4 18 36 VDC SYNC IN A0018538 A Ex d Ex t non Ex version B Ex de version Terminal 1 L supply voltage 18 to 36 VDC Terminal 2 L supply voltage 18 to 36...

Страница 9: ...the total weight consisting of the source container and the Gamma Modulator FHG65 Ensure sufficient stability is guaranteed Provide an additional support if necessary After mounting measure the local...

Страница 10: ...16L and 304 Water connection 2 x G 1 4 A DIN ISO 228 Outlet temperature max 40 C 104 F temperature monitoring is recommended Water pressure 4 to 6 bar 58 to 87 psi Water flow min 60 l h Drain sensor w...

Страница 11: ...32 20 9 560 22 0 142 5 59 142 5 59 172 6 77 172 6 77 572 22 5 144 5 67 144 5 67 495 19 5 524 20 6 537 21 1 A B 81 3 19 81 3 19 A0018530 2 Engineering unit mm in A Ex de version left without water cool...

Страница 12: ...2 87 A0018531 3 L angle bracket engineering unit mm in Weight Weight without water cooling jacket max 18 kg 39 69 lb Weight with water cooling jacket empty max 21 kg 46 31 lb Weight with water coolin...

Страница 13: ...6L 1 4404 8 Cooling water connection PA66 9 O ring FKM 70 10 Cover clamp 304 1 4301 1 4581 A2 Materials of the cable entry with seal Feature 040 Cable entry power supply Option A M20 gland 316L 1 4404...

Страница 14: ...d except in the event of strong electromagnetic interference Cable requirements Max capacitance 120 nF Max resistance 1000 Max inductance 0 65 mH Cable not shielded not twisted Signal transmission clo...

Страница 15: ...ty according to EN 61326 Appendix A Industrial and NAMUR Recommendation NE 21 Electrical connection Terminals Plug in screw terminals Wire cross section 1 0 to 2 5 mm2 17 to 13 AWG for power supply an...

Страница 16: ...itional upstream Synchronizer FHG66 All the Gamma Modulators connected to the synchronizers then run in common mode Cascading signal 12 V 5 mA Installation requirements Mounting location The Synchroni...

Страница 17: ...terminal blocks 2 Remove device Mechanical construction Dimensions 112 4 41 95 3 74 108 4 25 22 5 0 89 A B A B CASC_IN SYNC 1 SYNC 2 SYNC 3 A0018543 6 Engineering unit mm in Weight Weight approx 150 g...

Страница 18: ...1 B Error at SYNC 2 A and B Error at SYNC 3 A and B off but red LED on Error at cascading input CASC_IN Operating elements The DIP switches are located behind the swing down front panel ON OFF 1 2 3 4...

Страница 19: ...requirements of the EC Directives Endress Hauser confirms that the device has been successfully tested by applying the CE mark Explosion protection Gamma Modulator FHG65 Additional approvals Synchroni...

Страница 20: ...TI00439F Other documentation For an overview of the scope of the associated Technical Documentation refer to the following W M Device Viewer www endress com deviceviewer Enter the serial number from t...

Отзывы: