EngyCal
®
RH33
Wiring
Hauser
21
5
Wiring
5.1
Connection instructions
!
WARNING
Danger! Electric voltage!
‣
The entire connection of the device must take place while the device is de-energized.
!
CAUTION
Pay attention to additional information provided
‣
Before commissioning, ensure that the supply voltage corresponds to the specification on
the nameplate.
‣
Provide a suitable switch or power-circuit breaker in the building installation. This switch
must be provided close to the device (within easy reach) and marked as a circuit breaker.
‣
An overload protection element (rated current = 10 A) is required for the power cable.
For installing the BTU meter and the associated components, observe the general instructions
according to EN 1434 Part 6.
5.2
Quick wiring guide
1 5
6
2 52 53
+
3 7
8
4 54 55
+
+
+
U
I
10 11 50 51
60 61 62 63
1+
2+
1-
2-
70 71
80 81 82 81
90 91
LPS
R
13
R
14
R
23
R
24
L/+ N/-
T Warm
RTD or 0/4...20 mA
T Cold or Pressure
RTD or 0/4...20 mA
Flow
Pulse or 0/4...20 mA
2x Open Col.
2x Digital In
I/Pulse Out
Relay 1 Relay 2 Power
supply
+
-
1+ 1- 2+ 2-
+
-
A0022341
17
Connection diagram of the device
Terminal assignment