Ecograph T
8
Hauser
Installation conditions
Orientation
Position of use as per DIN 16 257, NL 90 ± 30°
Installation instructions
Panel cutout and installation / design, dimensions:
Installation depth: approx. 171 mm (6.73") (incl. terminals and fastening clips)
Panel cutout: 138
+1
x 138
+1
mm (5.43
+0.04
x 5.43
+0.04
")
Panel thickness: 2 to 40 mm (0.08 to 1.58")
Securing to DIN 43 834
!
Note!
A distance of min. 15 mm (0.59") between the devices has to be observed if aligning the devices in the Y-
direction (vertically above one another).
The devices can be arranged horizontally beside one another in the X direction without any spacing between
the devices.
Environment
Ambient temperature range
0 to 50 °C (32 to 122 °F)
Storage temperature
-20 to +60 °C (-4 to 140 °F)
Relative air humidity
0 to 50 °C (32 to 122 °F), max. 75% without condensation
Climate class
As per IEC 60654-1: B1
Degree of protection
Front-panel IP 54 (IEC 60529, Cat. 2) NEMA 2
rear-panel IP 20 (IEC 60529, Cat. 2)