background image

Ecograph T

2

Hauser

Function and system design

Measuring principle

Electronic acquisition, display, recording, analysis, remote transmission and archiving of analog and digital 
input signals.

Measuring system

Multi-channel data recording system with multi-coloured LCD display (120 mm / 4.7" screen size), 
galvanically isolated universal inputs (U, I, TC, RTD), digital input, transmitter power supply, limit relay, 
communication interfaces (USB, Ethernet, RS232/485), internal Flash memory and CompactFlash card. 100 
ms scan rate for all channels.  ReadWin

®

 2000 PC software for comprehensive offline device configuration and 

data analysis.

Block diagram

This block diagram is only indicative of the functionality.

Input 

Analog multi-function input 
channel 1-6

Measured variable, measuring range

To IEC 60873-1:
An additional display error of -/+ 1 digit is permitted for every measured value.
Measuring ranges which can be selected per channel:

*.csv
*.dat

E

LCD 4,7”
Display

115/230 V AC
24 V AC/DC

LCD 4,7”
Display

3/6 universal inputs:
- TC
- RTD
- mA
- mV, V

Optional:
- Integration
- Analysis

1 digital I/O:
- Event
- Time
- Counter
- Control function

Recording internal &
Compact Flash

Lockable cover

Display modes:
- Bargraph
- Trend
- Digital

Communication with PC /
Modem / Network:
- USB
- RS232/485
- Ethernet 10 Base T

Web-Browser function

4 Relays:
- 1 change-over contact
- 3 normally open contacts

14 limit values
(variable channel mapping)

1 x 24 V, 250 mA
Transmitter power
supply output

Measured 

variable

Measuring range

Maximum measured error 

of measuring range (oMR)

Input 

impedance

Current

0...20 mA
0...5 mA
4...20 mA
Overrange: up to 22 mA

± 0.10 %

Load: = 50 Ohm

Voltage  > 1 V

0...10 V
0...5 V
± 10 V
± 30 V

± 0.10 %

(

 980 kOhm

Содержание Ecograph T

Страница 1: ...rsatile up to 6 universal inputs record all measuring signals Clear layout multi coloured display digital bargraph and curve display Compact low installation depth saves space and money Safe reliable data archiving with internal memory and separate CompactFlash card mechanically locked No data loss even in event of power failure System enabled network integration and remote data transmission via E...

Страница 2: ...ction input channel 1 6 Measured variable measuring range To IEC 60873 1 An additional display error of 1 digit is permitted for every measured value Measuring ranges which can be selected per channel csv dat E LCD 4 7 Display 115 230 V AC 24 V AC DC LCD 4 7 Display 3 6 universal inputs TC RTD mA mV V Optional Integration Analysis 1 digital I O Event Time Counter Control function Recording interna...

Страница 3: ...1 1 Type R Pt13Rh Pt 50 to 1768 C 58 to 3214 F IEC581 1 0 15 oMR from 500 C 932 F 0 15 oMR from 500 C 932 F 0 15 oMR from 600 C 1112 F 0 15 oMR from 100 C 212 F 0 15 oMR from 100 C 212 F 2 7 MOhm Measured variable Measuring range Maximum measured error of measuring range oMR Input impedance Measured variable Limit values steady state without destroying input Cable open circuit detection line influ...

Страница 4: ... pulse counter 13 digit 64 bit operating time message operating time Functions of the control input start recording background illumination OFF operating lock time synchronization Output Auxiliary voltage output The auxiliary voltage is provided to activate the digital input or sensors with floating contacts and is galvanically isolated from the system and the inputs testing voltage 500 V The grou...

Страница 5: ...r contact Standard relay 3 relays with NO contact for limit value messages can be configured as NC contact Note It is not permitted to mix low voltage and safety extra low voltage do not mix SELV circuits and low voltage Response time 1 s Maximum DC contact load 50 V 300 mA steady state without destroying input Maximum AC contact load 230 V 3 A steady state without destroying input ...

Страница 6: ...0 mA 0 5 mA Typ J K T N L D C B S R 91 10 k _ _ 12 V 24 VDC 24 V AC DC 50 60 Hz 5 6 9 1 x11 x12 x13 x14 x15 x16 U 1V TC GND RxD TxD RxD TxD Ethernet RS232 41 42 31 32 21 22 11 13 12 L N PE Rel4 Rel3 Rel2 Rel1 CH 4 CH 5 CH 6 RS485 611 612 613 614 615 616 511 512 513 514 515 516 411 412 413 414 415 416 CH 1 CH 2 CH 3 111 112 113 114 115 116 211 212 213 214 215 216 311 312 313 314 315 316 Volt drop 1...

Страница 7: ...ess via setup menu in device The device can be connected to devices in an office environment with this interface For safe spacing distances observe the office equipment standard IEC 60950 1 Direct connection to a PC is possible with a crossover cable The device can be used in the network as a Web server Two Ethernet function LEDs on the rear of the device Serial RS232 RS485 interface option Rear m...

Страница 8: ... Note A distance of min 15 mm 0 59 between the devices has to be observed if aligning the devices in the Y direction vertically above one another The devices can be arranged horizontally beside one another in the X direction without any spacing between the devices Environment Ambient temperature range 0 to 50 C 32 to 122 F Storage temperature 20 to 60 C 4 to 140 F Relative air humidity 0 to 50 C 3...

Страница 9: ...ation IEC 61000 4 11 40 0 Emission To IEC 61326 Class A operation in industrial environment Interference voltage Mains line To CISPR 16 1 2 Class A Interference current Ethernet line To EN 50022 Class A Interference field intensity Housing all connections to CISPR 16 Class A Interference voltage suppression Common mode interference voltage suppression IEC 61298 3 analog inputs 80 dB at 60 V and 50...

Страница 10: ...y non volatile Main memory 2 MB SRAM Data buffering and RTC buffering with lithium cell replace after 10 years External memory Cyclic copying of the measured data for archiving on CompactFlash card CompactFlash base type I Supported CF memory cards 32 MB 64 MB 128 MB 256 MB and 512 MB Please use genuine CF cards from the manufacturer see Accessories If no CF memory card is present in the slot inte...

Страница 11: ...ace RS232 RS485 e g modem Ethernet or front mounted USB port Analog inputs Memory cycle 5 min Memory cycle 1 min Memory cycle 30 s Memory cycle 10 s Memory cycle 1 s 1 19973 days 21h 4443 days 3 h 2221 days 13 h 740 days 12 h 74 days 1 h 3 9987 days 8 h 2111 days 8 h 1055 days 16 h 351 days 21 h 35 days 4 h 6 5707 days 9 h 1182 days 5 h 591 days 2 h 197 days 19 days 16 h Analog inputs Memory cycle...

Страница 12: ...e USB connection incl connecting cable 14 limit values can be freely defined PC software package CompactFlash CF slot Input signal A 3 universal U I TC RTD B 6 universal U I TC RTD Power supply 1 115 230 V AC 50 60 Hz 2 24 V AC DC 50 60 Hz Interface A USB B USB RS232 485 Ethernet Memory medium 1 without CF card 2 CF card 64 MB 3 CF card 256 MB Housing A Panel 144x144 mm 5 67 x 5 67 IP54 NEMA 2 B P...

Страница 13: ...0078843 Terminal pluggable 3 pole for power supply 51009211 Terminal pluggable 6 pole for analog input 51009214 Terminal pluggable 3 pole for relay 51009215 Terminal pluggable 6 pole for relay 51009210 Terminal pluggable 3 pole for digital I O 51007892 CompactFlash CF memory card 64 MB 51009640 CompactFlash CF memory card 256 MB RSG30A S1 RS232 interface cable 9pol to PC connection RSG30A S2 RS232...

Страница 14: ...uarter Endress Hauser GmbH Co KG Instruments International Colmarer Str 6 79576 Weil am Rhein Deutschland Tel 49 76 21 9 75 02 Fax 49 76 21 9 75 34 5 www endress com info ii endress com TI115R 09 en 02 06 51009568 FM SGML 6 0 ProMoDo ...

Отзывы: