25
PRESSURE FULL (015)
For displaying and querying the value entered for the PRESSURE FULL parameter (BASIC
SETUP group).
Options:
• Valid: Select this option if the selected and desired value is displayed.
• Not valid: Select this option if an incorrect value or a value that was not selected is
displayed. In this case, operation of the device in the safe measuring mode is not
possible.
FULL CALIBRATION (017)
For displaying and querying the value entered for the FULL CALIBRATION parameter
(BASIC SETUP group).
Options:
• Valid: Select this option if the selected and desired value is displayed.
• Not valid: Select this option if an incorrect value or a value that was not selected is
displayed. In this case, operation of the device in the safe measuring mode is not
possible.
SET LRV (021)
For displaying and querying the value entered for the SET LRV parameter (BASIC SETUP
group).
Options:
• Valid: Select this option if the value entered and desired is displayed.
• Not valid: Select this option if a value that was not entered or desired is displayed.
In this case, operation of the device in the safe measuring mode is not possible.
SET URV (022)
For displaying and querying the value entered for the SET URV parameter (BASIC SETUP
group).
Options:
• Valid: Select this option if the value entered and desired is displayed.
• Not valid: Select this option if a value that was not entered or desired is displayed.
In this case, operation of the device in the safe measuring mode is not possible.
DAMPING VALUE (855)
For displaying and querying the value entered for the DAMPING VALUE parameter
(BASIC SETUP group).
Options:
• Valid: Select this option if the value entered and desired is displayed.
• Not valid: Select this option if a value that was not entered or desired is displayed.
In this case, operation of the device in the safe measuring mode is not possible.
!
Note!
Changing the "Damping" DIP switch on the electronic insert does not have any effect on
the damping time when operation is locked. A change only takes effect once operation
has been unlocked.
CONF. PASSWORD (856)
Once the safety-related parameters have been successfully interrogated, the password
" 7452" must be entered again via the CONF. PASSWORD parameter. Afterwards, the
device is locked for the safe measuring mode. The SAFETY LOCKSTATE parameter
displays the status "Locked".
MEASURING MODE = Level, LEVEL SELECTION = Level Easy Pressure
Parameter name
Description