Use in protective systems
Proline Prosonic Flow P 500 HART
24
Hauser
To check that values are displayed correctly, the following string appears on the device display
or operating tool:
012-.
5. The user must confirm that the values are displayed correctly.
The device displays the current settings for the following parameters one after
another for the user to confirm each of them:
Installation
direction
Creeping quantity
suppression
Confirmation
of correct
sensor installation
Parameters for the
measuring point
configuration
Current output
parameter
A0044363-EN
For detailed information on the parameters in the graphic, see the Operating
Instructions.
6. At the end of the verification, the SIL locking code
7452
must be entered in the
Set
write protection
parameter again to confirm that all the parameter values have been
defined correctly.
If the SIL locking code has been entered correctly, the message
"End of sequence"
appears on the display.
7. Press the key to confirm.
The SIL mode is now activated.
Recommendation:
ON
OFF
1
2
3
4
A0029630
1
Proline 500
1. Check the write protection switch (WP) in the connection compartment.
2. Set this switch to the
ON
position where necessary.
Hardware write protection enabled.
3. Restart the device on completion of the SIL confirmation sequence.